REG-UM-00836-EN-12 (August 2018)
User Manual
Industrial Registers
Model ER-9 Digital Resettable Totalizer and
Rate of Flow Indicator, Plus Pulse Output
ER-9 Indicator
ER-9 Register
For Portable Large Meter Tester
Страница 1: ...M 00836 EN 12 August 2018 User Manual Industrial Registers Model ER 9 Digital Resettable Totalizer and Rate of Flow Indicator Plus Pulse Output ER 9 Indicator ER 9 Register For Portable Large Meter Te...
Страница 2: ...Industrial Registers Model ER 9 Digital Resettable Totalizer Page ii August 2018 REG UM 00836 EN 12...
Страница 3: ...ons 7 Wiring Terminals 7 Transmitter Connections 7 Operation 8 Display Types 8 Control Keys 8 Programming 9 Totalizer Programming 10 Rate of Flow Programming 10 Pulse Output Programming 11 Troubleshoo...
Страница 4: ...Industrial Registers Model ER 9 Digital Resettable Totalizer Page iv August 2018 REG UM 00836 EN 12...
Страница 5: ...tput It has independent programmable scale factors for rate and totalization allowing you to program these displayed values in different but meaningful engineering units such as gallons per minute and...
Страница 6: ...lace batteries before they are completely exhausted to retain programming and indicated volume If two batteries are present remove and replace one battery at a time If only one battery is present inst...
Страница 7: ...inal numbers on the ER 9 Connect the wire coming from the transmitter to the corresponding terminal number for the ER Remote models Connecting to a Generic Reed Switch To connect a generic reed switch...
Страница 8: ...he Flow Total and the Flow Rate The letter R on the left of the screen indicates that the Flow Rate is being displayed Programming mode The Down Arrow key toggles the unit between the Total Display an...
Страница 9: ...he decimal point on the totalizer display from no decimal OFF to 0 00000 R 3 1 000 Mode 3 Rate Scale Factor Decimal Point sets the decimal in Rate Scale Factor number from no decimal to 0 000 R 4 9999...
Страница 10: ...asure for any time base such as gallons minute liters second barrels hour Rate scale factor To determine the Rate Scale Factor Program Mode 4 use the following formula Rate Scale Factor Seconds Transm...
Страница 11: ...L 198 340 52 396 1484 689 3 4 35 RCDL 126 671 33 463 947 566 1 40 RCDL 89 781 23 717 671 610 1 55 RCDL 58 064 15 339 434 351 1 70 RCDL 46 752 12 350 349 726 1 1 2 120 RCDL 23 867 6 305 178 539 2 170 R...
Страница 12: ...ctions 3 Repair or replace transmitter Cannot program Program enable jumper is not installed or is installed improperly Install jumper Cannot reset from front panel Reset enable is not programmed Repr...
Страница 13: ...calibrated vessel 5 Determine the number of pulses per gallon by dividing the indicator reading by the number of gallons of fluid in the vessel Use this value for your calculations Example You progra...
Страница 14: ...assemble the unit Disc meter 1 Remove the front cover on the ER 9 unit and disconnect the sensor wiring 2 Loosen the side seal screw on the assembly adapter twist the adapter 90 and lift the entire ac...
Страница 15: ...Power Source Type Dual 3V Lithium battery Replacement part 62576 001 Battery life expectancy 5 years typical if using external DC supply 6 months if used alone with 50 duty cycle output Low power ind...