Detailed Description
2.1 Various interface signals and functions (A2)
Basic logic functions: NC/PLC interface signals (Z1)
Function Manual, 11/2006, 6FC5397-0BP10-2BA0
11
DB10
DBX109.0
NCK alarm is active
Edge evaluation: no
Signal(s) updated: cyclic
Signal state 1 or
edge change 0 → 1
At least one NCK alarm is present.
This is a group signal for the interface signals
(DB21, ... DBX36.6 (channelspecific NCK alarm is active)
of all existing channels.
Signal state 0 or
edge change 1 → 0
No NCK alarm is active.
Corresponding to .... DB21, ... DBX36.6 (channelspecific NCK alarm present)
DB21, ... DBX36.6 (NCK alarm with processing stop present)
References
/DA/ Diagnostics Guide
DB10
DBX109.5
Heatsink temperature alarm, NCU 573
Edge evaluation: no
Signal(s) updated: cyclic
Signal state 1 or
edge change 0 → 1
The limit values of the heatsink temperature were exceeded on the NCU 573.
The heatsink monitoring function has responded and the continuous operation of the operator
panel is no longer assured.
Signal state 0 or
edge change 1 → 0
The heatsink monitoring function of the NCU 573 has not responded.
DB10
DBX109.6
Air temperature alarm
Edge evaluation: no
Signal(s) updated: cyclic
Signal state 1 or
edge change 0 → 1
The ambient temperature or fan monitoring function has responded.
This could be due to the following:
•
The temperature monitoring has identified an ambient temperature that is too high (approx. 60
°C). Alarm 2110 "NCK temperature alarm" is output.
•
The speed monitoring of the 24 V DC fan used to cool the module has responded. Alarm 2120
"NCK fan alarm" is output.
Measures: Replace the fan and/or ensure that additional ventilation is provided.
When a temperature or fan error responds, a relay contact (terminal 5.1, 5.2 or 5.1, 5.3) in the
infeed/regenerative feedback unit is activated which can be evaluated by the customer.
Signal state 0 or
edge change 1 → 0
Neither the temperature monitoring nor the fan monitoring has responded.
Application
example(s)
Appropriate measures can be initiated by the PLC user program if the temperature or fan
monitoring is activated.
Corresponding to .... When a temperature or fan error responds, a relay contact (terminal 5.1, 5.2 or 5.1, 5.3) in the
infeed/regenerative feedback unit is activated. This can be evaluated.
References
/DA/ Diagnostics Guide
Summary of Contents for SINUMERIK 840D sl
Page 282: ...Index Basic logic functions Acceleration B2 64 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 388: ...Basic logic functions Travel to fixed stop F1 Function Manual 11 2006 6FC5397 0BP10 2BA0 52 ...
Page 962: ...Index Basic logic functions Emergency Stop N2 20 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 1704: ...Constraints Basic logic functions Spindles S1 94 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 1716: ...Index Basic logic functions Spindles S1 106 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 1996: ...Index Basic logic functions Tool Offset W1 208 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 2150: ...Table of contents Basic logic functions Appendix 4 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 2184: ...Glossary Basic logic functions Appendix 38 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...