Detailed description
2.12 Block descriptions
Basic logic functions: PLC Basic program powerline (P3 pl)
200
Function Manual, 11/2006, 6FC5397-0BP10-2BA0
2.12.16
FC 10: AL_MSG error and operating messages
Description of Functions
FC AL_MSG evaluates the signals entered in DB 2 and displays them as incoming and
outgoing error and operational messages on the MMC.
The incoming signals (positive edge)
are displayed immediately in the case of both error and operating messages.
Outgoing signals (negative edge)
are only canceled immediately in the case of operating messages. In case of error
messages, the messages not needed any more are deleted only with the parameter "Quit"
i.e. error messages remain stored on the MMC - even if the signals no longer exist - until the
"acknowledge" parameter is issued, i.e., until the user acknowledges the messages.
The "ToUserIF" parameter can be used to transfer the group signals for the feed, read and
NC start disabling signals and feed stop signal to the existing axis, spindle and channel
interfaces. The group signals are transferred to the user interface directly from the status
information in DB 2 irrespective of an alarm acknowledgment.
1.
If parameter "ToUserIF": is set to FALSE, signals are not transferred to the user interface.
In this case, the user must take measures in his PLC program to ensure that these
signals are influenced in the interface.
2.
If parameter "ToUserIF": is set to TRUE, all signals listed above are sent to the user
interface as a group signal in each case. The user PLC program can therefore influence
these signals only via DB 2 in connection with a message or alarm output. The
appropriate information is overwritten in the user interface.
As an alternative to the procedure described under paragraph 2, the user can influence the
disable and stop signals without a message output by applying a disable or stop signal state
to the interface signals after FC AL_MSG has been called.
The following program illustrates this method:
CALL FC 10 (
ToUserIF := TRUE,
Ack :=
I 6.1);
u m 50.0;
//Feed disable for channel 1
to DB 21;
s dbx 6.0;
//Set disable condition, reset via
//FC AL_MSG, if M 50.0 outputs the signal "0".
The error and operational messages are stored by the user in the data block DB 2, so that a
message can also be displayed at MMC.
Summary of Contents for SINUMERIK 840D sl
Page 282: ...Index Basic logic functions Acceleration B2 64 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 388: ...Basic logic functions Travel to fixed stop F1 Function Manual 11 2006 6FC5397 0BP10 2BA0 52 ...
Page 962: ...Index Basic logic functions Emergency Stop N2 20 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 1704: ...Constraints Basic logic functions Spindles S1 94 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 1716: ...Index Basic logic functions Spindles S1 106 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 1996: ...Index Basic logic functions Tool Offset W1 208 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 2150: ...Table of contents Basic logic functions Appendix 4 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...
Page 2184: ...Glossary Basic logic functions Appendix 38 Function Manual 11 2006 6FC5397 0BP10 2BA0 ...