05.05
Parameter list
SIEMENS AG 6RX1700-0AD76
11-75
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P701
FDS
(G113)
Normalization of "Main setpoint" analog input
This parameter specifies the percentage value which is generated for an
input voltage of 10V (or an input current of 20mA) at the analog input.
The following generally applies:
For voltage input:
P
V
Y
X
701
10
[%]
=
∗
X .. Input voltage in volts
Y .. % value which is generated for input
voltage
X
With current input:
P
mA
Y
X
701
20
[%]
=
∗
X .. Input current in mA
Y .. % value which is generated for input
current X
-1000.0 to 1000.0
[%]
0.1%
Ind: 4
FS=100.0
Type: I2
P052 = 3
P051 = 40
Online
P702
(G113)
Offset for "Main setpoint" analog input
-200.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
P703
*
(G113)
Mode of signal injection at "Main setpoint" analog input
0 = Injection of signal with sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P704
*
(G113)
Source for selection of sign reversal at "Main setpoint" analog input
Selection of binector to control
sign reversal at the analog input
("1" state
= reverse sign)
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P705
(G113)
Filtering time for "Main setpoint" analog input
Note: Hardware filtering of approximately 1 ms is applied as standard.
0 to 10000
[ms]
1ms
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P706
*
(G113)
Source for enabling of "Main setpoint" analog input
Selection of binector to control
enabling of the analog input
("1" state =
enabled)
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......