05.05
Start-Up
SIEMENS AG 6RX1700-0AD76
7-37
SIMOREG DC Master Operating Instructions
Diagnostic parameter n732:
Indices i001 to i032 apply to a CBC as the first communication board; indices i033 to i064 apply to
a CBC as the second communication board.
Value
Meaning
n732.001
or
n732.033
0
1
2
5
7
13
14
15
20
21
22
23
35
36
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
1
23
35
257
258
273
274
513
514
529
530
769
770
785
786
1025
1026
1041
1042
1092
No fault
Fault F080/fault value 5 is displayed under fault conditions:
Fault values for CAN layer 2:
Incorrect address on CAN Bus (P918 / slave address)
Incorrect CAN identifier with PKW Request (U711)
Incorrect CAN identifier with PKW Request-Broadcast (U719)
Incorrect CAN identifier with PZD Receive (U712)
Incorrect CAN identifier with PZD Transmit (U713)
PZD transmit length = 0 (U714)
PZD transmit length > 16 , i.e. too long (U714)
Incorrect CAN identifier with PZD Receive-Broadcast (U716)
Incorrect CAN identifier with PZD Receive-Multicast (U717)
Incorrect CAN identifier with PZD Receive-Internode (U718)
Invalid baud rate (U720)
Incorrect CAN protocol type (U721)
PKW Request-Broadcast (U719) without PKW Request (U711)
Overlap between CAN identifier PKW and PKW Broadcast
Overlap between CAN identifier PKW and PZD Receive
Overlap between CAN identifier PKW and PZD Transmit
Overlap between CAN identifier PKW and PZD Receive-Broadcast
Overlap between CAN identifier PKW and PZD Receive-Multicast
Overlap between CAN identifier PKW and PZD Receive-Internode
Overlap between CAN identifier PKW Broadcast and PZD Receive
Overlap between CAN identifier PKW Broadcast and PZD Transmit
Overlap between CAN identifier PKW Broadcast and PZD Receive-Broadcast
Overlap between CAN identifier PKW Broadcast and PZD Receive-Multicast
Overlap between CAN identifier PKW Broadcast and PZD Receive-Internode
Overlap between CAN identifier PZD Receive and PZD Transmit
Overlap between CAN identifier PZD Receive and PZD Receive-Broadcast
Overlap between CAN identifier PZD Receive and PZD Receive-Multicast
Overlap between CAN identifier PZD Receive and PZD Receive-Internode
Overlap between CAN identifier PZD Transmit and PZD Receive-Broadcast
Overlap between CAN identifier PZD Transmit and PZD Receive-Multicast
Overlap between CAN identifier PZD Transmit and PZD Receive Internode
Overlap between CAN identifier PZD Receive-Broadcast and PZD Receive-Multicast
Overlap between CAN identifier PZD Receive-Broadcast and PZD Receive-Internode
Overlap between CAN identifier PZD Receive-Multicast and PZD Receive-Internode
Fault values for CANopen:
Incorrect bus address (P918)
Invalid baud rate (U720)
Incorrect CAN protocol type (U721)
Invalid mapping of 1st Receive PDO (U711)
Invalid transmission type of 1
st
Receive PDO (U711)
Invalid mapping of 1
st
Transmit PDO (U715)
Invalid transmission type of 1
st
Transmit PDO (U715)
Invalid mapping of 2
nd
Receive PDO (U712)
Invalid transmission type of 2
nd
Receive PDO (U712)
Invalid mapping of 2
nd
Transmit PDO (U716)
Invalid transmission type of 2
nd
Transmit PDO (U716)
Invalid mapping of 3
rd
Receive PDO (U713)
Invalid transmission type of 3
rd
Receive PDO (U713)
Invalid mapping of 3
rd
Transmit PDO (U717)
Invalid transmission type of 3
rd
Transmit PDO (U717)
Invalid mapping of 4
th
Receive PDO (U714)
Invalid transmission type of 4
th
Receive PDO (U714)
Invalid mapping of 4
th
Transmit PDO (U718)
Invalid transmission type of 4
th
Transmit PDO (U718)
Invalid Life Time Event or incorrect basic unit parameterized (U719)
n732.002
or
n732.034
Number of correctly received PZD CAN telegrams since Power ON
Irrelevant for CANopen
n732.003
or
n732.035
Number of PZD telegrams lost since Power ON
Telegrams will be lost if the CAN Bus master sends PZD telegrams faster than they can
be processed by the slave.
Irrelevant for CANopen
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......