Parameter list
05.05
11-38
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P230
FDS
(G152)
Setting period of speed controller integrator
[SW 1.9
and later]
After a positive edge at the binector set in P695, the integrator of the speed
controller is set to the instantaneous value of the connector set in P631.
If a time of > 0 is set on P230, this setting operation is not performed just
once, but the speed controller integrator is set continually to the setting
value for the parameterized time period.
0 to 10000
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
on-line
P234
*
FDS
(G152)
Set speed controller P component to zero
0
Set controller P component to zero (i.e. to obtain a pure I
controller)
1
Controller P component is active
0 to 1
1
Ind: 4
FS=1
Type: O2
P052 = 3
P051 = 40
Offline
P236
*
FDS
Specifying the dynamic response of the speed control loop
[SW 2.0 and later]
The parameter value is used as the optimization criterion for the speed
control loop.
Note:
Changes to this value do not take effect until the speed controller
optimization run (P051 = 26, see Section 7.5) has been executed.
Setting instructions:
-
For drives, for example, with gear backlash, optimization should be
started with low dynamic response values (from 10%).
-
For drives with top synchronism and dynamic response requirements,
values up to 100% should be used.
10 to 100
[%]
1
Ind: 4
FS=75
Type: O2
P052 = 3
P051 = 40
online
11.13 Closed-loop field current control, field gating unit
P250
FDS
(G166)
Alpha G limit (field)
Rectifier stability limit for firing angle of field converter
0 to 180
[degrees]
1 degree
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P251
FDS
(G166)
Alpha W limit (field)
Inverter stability limit for firing angle of field converter
0 to 180
[degrees]
1 degree
Ind: 4
FS=180
Type: O2
P052 = 3
P051 = 40
Online
P252
*
FDS
(G166)
Filtering of line frequency correction (field)
The internal line synchronization for the field gating pulses derived from the
field mains infeed terminals is filtered with this time constant. In operation
on "weak" power supplies with unstable frequencies, for example, on a
diesel-driven generator (isolated operation), the filter time constant must be
set lower than for operation on "constant V/Hz" systems in order to achieve
a higher frequency correction speed.
Using the units position, the line synchronization function can be altered
additionally as follows:
When the parameter is set to an uneven number, the measured line zero
crossings for line synchronization are subjected to an extra "filter", may
improve performance in the case of difficulties with brief mains interruptions
(e.g. power supply via sliding current collectors), but may only be set for
constant V/Hz power supplies (not for weak isolated supply systems).
0 to 200
[ms]
1ms
Ind: 4
FS=200
Type: O2
P052 = 3
P051 = 40
Offline
P253
*
FDS
(G166)
Control word for field precontrol
0
Field precontrol disabled, precontrol output = 180°
1
Field precontrol active, output is dependent on field current
setpoint, field line voltage, P112
0 to 1
1
Ind: 4
FS=1
Type: O2
P052 = 3
P051 = 40
Offline
P254
*
FDS
(G166)
Set field current controller I component to zero
0
Set controller I component to zero (i.e. to obtain pure P
controller)
1
Controller I component is active
0 to 1
1
Ind: 4
FS=1
Type: O2
P052 = 3
P051 = 40
Offline
P255
FDS
(G166)
Field current controller P gain
This parameter is set automatically during the optimization run for precontrol
and current controller (armature and field) (P051=25).
0.01 to 100.00
0.01
Ind: 4
FS=5.00
Type: O2
P052 = 3
P051 = 40
Online
P256
FDS
(G166)
Field current controller reset time
This parameter is set automatically during the optimization run for precontrol
and current controller (armature and field) (P051=25).
0.001 to 10.000
[s]
0.001s
Ind: 4
FS=0,200
Type: O2
P052 = 3
P051 = 40
Online
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......