Start-Up
05.05
7-18
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
13
Documentation of setting values
•
Read out parameters with DriveMonitor (see Section 15 “DriveMonitor”)
or
•
Document
parameters
If P052=0, only parameters that are not set to the default setting are displayed on the operator
control panel.
7.6
Manual optimization (if required)
7.6.1
Manual setting of armature resistance RA (P110) and armature inductance
LA (P111)
•
Setting of armature circuit parameters according to motor list
Disadvantage: The data is very inaccurate and/or the actual values deviate significantly.
The feeder resistances are not taken into account in the armature circuit resistance.
Additional smoothing reactors and feeder resistances are not taken into account in the armature
circuit inductance.
•
Rough estimation of armature circuit parameters from motor and supply data
Armature circuit resistance P110
(P100)
[A]
current
armature
motor
Rated
10
(P101)
[V]
voltage
armature
motor
Rated
]
[
Ω
R
A
∗
=
The basis for this formula is that 10% of the rated armature voltage drops across armature
circuit resistor R
A
at rated armature current.
Armature circuit inductance P111
(P100)
[A]
current
armature
motor
Rated
(P071)
[V]
section
power
armature
of
voltage
supply
converter
Rated
1.4
[mH]
L
A
∗
=
The basis for this formula is the empirical value: The transition from discontinuous to continuous
current is at approx. 30% of the rated motor armature current.
•
Calculation of armature circuit parameters based on current/voltage measurement
−
Select current-controlled operation:
P084=2
−
Set
parameter
P153=0
(precontrol deactivated)
−
The field must be switched off by setting
P082=0
and, in the case of excessively high
residual flux, the rotor of the DC motor locked so that it cannot rotate.
−
Set the overspeed protection threshold
P354=5%
−
Enter a main setpoint of 0
−
If ”ENABLE OPERATION” is applied and the “SWITCH ON” command entered, an armature
current of approximately 0% now flows.
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......