05.05
Function descriptions
SIEMENS AG 6RX1700-0AD76
9-5
SIMOREG DC Master Operating Instructions
Example 2:
The contents of connectors K0401 and K0402 must be output on the connector displays
(parameter r043)
The following settings need to be made to create the correct links:
P044.index01 = 401: Links connector K0401 to the 1
st
connector display
P044.index02 = 402: Links connector K0402 to the 2
nd
connector display
Section 8, Sheet G121:
.01
.02
.03
.04
.05
.06
.07
P044 (0)
K
K
K
K
K
K
K
r043.01
r043.02
r043.03
r043.04
r043.05
r043.06
r043.07
401
402
The following values are now displayed in parameter r043:
r043.index01: Contents of connector K0401
r043.index02: Contents of connector K0402
r043.index03
to
r043.index07: Parameter P044.index.03 to 07 remain at the works setting (0) (value in
brackets next to parameter number) in this example, i. e. the contents
of connector K0000 (=fixed value 0) are displayed on r043.index.03 to
.07.
Setting parameters
(see also Section "Data sets")
In addition to the parameters that are used to select a signal (connector, binector), there are also
parameters which define an operating mode or the parameter value of some function.
Representation in function diagrams:
Apart from parameter numbers, the function diagrams may also contain the factory setting, function
and value range of parameters as supplementary information.
P109 (0)
Setting parameter
Parameter number = P109, factory setting = 0
P462.F(10.00s)
(0.01...300.00s)
Ramp-up time
Setting parameter in function parameter set (".F" after parameter number)
Parameter number = P462, factory setting = 10.00s
Value range = 0.01...300.00s
Parameter for setting ramp-up time
Examples:
P700 in Section 8, Sheet G113 defines the signal type of the analog input
(voltage input
±
10V, current input 0...20mA, current input 4...20mA).
P705 in Section 8, Sheet G113 defines the filter time for the analog input (adjustable
in ms).
Parameters P520 to P530 in Section 8, Sheet G153 determine the shape of the friction
characteristic.
P465 in Section 8, Sheet G126 determines whether the time settings must be multiplied
by a factor of 1 or 60.
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......