05.05
Connections
Siemens AG 6RX1700-0AD76
6-23
SIMOREG DC Master Operating Instructions
6.3.2.2 Operating mode "N+1 mode" (Redundancy mode of the armature supply)
Master Standby
master
Slaves
U800 = 1 Paralleling interface
active
U800 = 2 if a SIMOREG CCP is
used
U800 = 2 Paralleling interface active
Use master firing pulses
U803 = 1 "N+1 mode" active
U804.01 = 30 control word 1
U804.02 = 31 control word 2
U804.03 = 167 actual speed value
U804.04 = any
U804.05 = any
U804.06 = 32 status word 1
U804.07 = any
U804.08 = any
U804.09 = any
U804.10 = any
U804.01 = 32 status word 1
U804.02 = any
U804.03 = any
U804.04 = any
U804.05 = any
U804.06 = 30 control word 1
U804.07 = 31 control word 2
U804.08 = 167 actual speed value
U804.09 = any
U804.10 = any
U804.01 = 32 status word 1
U804.02 = any
U804.03 = any
U804.04 = any
U804.05 = any
U804.06 = any
U804.07 = any
U804.08 = any
U804.09 = any
U804.10 = any
U805 = 1 (bus termination)
on the two end units
(at both physical ends of the bus cable)
0 (no bus termination)
on all other units
U806.01 = 12 1 slave
13 2 slaves
14 3 slaves
15 4 slaves
16 5 slaves
U806.02 = 2 slave 2
U806.01 = 2 slave 2
U806.02 = 12 1 slave
13 2 slaves
14
3 slaves
15 4 slaves
16 5 slaves
U806.01 = 3
2 slaves
U806.01 = 3 and 4
3 slaves
U806.01 = 3,4 and 5
4 slaves
U806.01 = 3,4,5 and 6 5 slaves
U806.02 = set like U806.01
P082 <> 0 operating mode for
field
P082 = 0
internal field is not used
P083, set according to source of the actual speed value
P083 = 4
Freely connected
actual speed value
P609 = 6023 Use actual speed
value of master
P100 =
units
SIMOREG
of
Number
current
motor
Rated
P648, P649, set according to source of the control word
P648 = 6021 Use control word 1
from master
P649 = 6022 Use control word 2
from master
P821.01 = 31 Suppress alarm
A031
U807 = 0.000s telegram failure does not lead to a fault message
P110 = Actual armature resistance
x no. of SIMOREG converters
P111 = Actual armature
inductance
x no. of SIMOREG
converters
The optimization run for current
controller and precontrol
(P051 = 25) sets these parameters
correctly.
P110 = set as on master
P111 = set as on master
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......