Connectors and binectors
05.05
12-8
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Connector Description
Normalization
Function
diag., Sheet
K0454
Setting value for the n controller I component
16384
=
∧
100% of P100
G150
4-step master switch
[SW 1.7 and later]
K0510
Setpoint of the 4-step master switch
16384
=
∧
100%
G125
Connectors for SIMOREG CCP
[SW 2.1 and later]
K0574 -
K0577
See Operating Instructions SIMOREG CCP
General connectors
K0800
Operating status (code number) with one decimal place
K0801
Latest fault and alarm message
Low byte: Latest alarm message
If several alarms are active simultaneously, the alarm with the
lowest number if displayed here.
Value "0" means that no alarm is active.
High byte: Latest fault message
Value "0" means that no fault is active.
G189
K0810
Limitation bits
The meaning of these bits is described in Section 11, Parameter List, under
parameter r040.
K0900
Optimization run, setpoint 0
K0901
Optimization run, setpoint 1
K0902
Optimization run, setpoint 2
K0903
Optimization run, setpoint 3
K0904
Optimization run, setpoint 4
Connectors for raw data of pulse encoder evaluation
K0910
Measuring time for speed evaluation of pulse encoder
1 corresponds to 41.6666 ns if K0912 = xxxx xx0x (divisor 1:1)
1 corresponds to 83.3333 ns if K0912 = xxxx x01x (divisor 1:2)
1 corresponds to 166.666 ns if K0912 = xxxx x11x (divisor 1:4)
This value is always slightly higher than the measuring time set in P147.
G145
K0911
Number of pulses during measuring time set in K0910
The speed of the pulse encoder can be calculated from connectors K0910,
K0911 and K0912 by the following equation:
time
.
Meas
encoder
of
.
no
Pulse
000
000
24
0911
K
]
s
/
rev
[
n
act
∗
∗
=
Pulse number of encoder = 1*P141,
if K0912 = xx0x xxxx (1x evaluation)
Pulse number of encoder = 2*P141,
if K0912 = x01x xxxx (2x evaluation)
Pulse number of encoder = 4*P141,
if K0912 = x11x xxxx (4x evaluation)
Meas. time = 1* K0910 if K0912 = xxxx xx0x (divisor 1:1)
Meas. time = 2* K0910 if K0912 = xxxx x01x (divisor 1:2)
Meas. time = 4* K0910 if K0912 = xxxx x11x (divisor 1:4)
G145
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......