Installation
01.04
5-28
Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Supplementary boards may be inserted in any slot subject to the following restrictions:
NOTICE
♦
Slot 3 must not be used until slot 2 is already occupied.
♦
A technology board must always be installed in board location 2 of the electronics box.
♦
If a technology board is used in conjunction with
one
communication board, then the
communication board must be fitted in slot G (miniature-format boards, for example CBP2
and CBC) or slot 3 (large-format board SCB1).
A type
T400
technology module can also be used with
two
communication boards of type
CBC, CBD or CBP2 (see Section 7.7.1, Procedure for starting up technology boards).
♦
It is not possible to operate boards EB1, EB2, SLB and SBP in conjunction with a technology
board.
♦
The data of large-format boards are always output under slot E or slot G, i.e. the software
version of a technology board, for example, is displayed in r060.003.
♦
In addition to the LBA, miniature-format boards (for example CBP2 and CBC) also require an
ADB
(adapter board, support board). Due to their very compact physical dimensions, these
boards must be inserted in an ADB before they can be installed in the electronics box.
♦
A total of two supplementary boards of the same type can be used (e.g. 2 EB1s), but only 1
SBP and 1 SLB may be installed.
The diagram below shows which locations or slots can be used for the supplementary boards you
wish to install and which board combinations are possible:
Use TB?
TB on its own?
yes
yes
TB in slot 2
Required: LBA
Only one of the following
boards can be used in
addition to the TB:
CBC, CBD, CBP2,
SCB1
TB in location 2 and
CBC, CBD, CBP2 in slot G
with ADB in location 3 or
SCB1 in location 3.
Exception: T400 with two
communication modules
(see Section 7.7.1,
Procedure for starting up
technology boards)
no
no
Required: LBA and ADB
(for CBx only)
SCB1 in lacation 2
Use SCB1?
yes
no
SCB1 on its own?
yes
no
Required: LBA
One of the miniature-format
boards CBC, CBD, CBP2,
EB1, EB2, SLB or SBP can
be installed in addition to SCB1.
SCB1 can be installed in
either location 2 or lacation 3.
The ADB required for the other
board(s) is then inserted in the
other location in each case.
Required: LBA and ADB
(for miniature-format boards
only)
A maximum total of 4 boards
can be installed, these may
include no more than two of
the miniature-format boards
CBC, CBD, CBP2, EB1 and
EB2 or one of the miniature-
format boards SLB or SBP.
A maximum of two miniature-
format boards may be inserted
in the ADB.
Location 3 may not be used
unless a board has already
been inserted in lacation 2.
Required: LBA and ADBs
(depending on number of
miniature-format boards)
TB = T100, T300 or T400
For information about starting up supplementary boards, please refer to Section 7.7 "Starting up
optional supplementary boards".
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......