Faults / Alarms
05.05
10-24
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
5
Parameters P918, U711 to U721 are not correctly set or
not accepted after a change by means of U710 = 0
setting. (The meanings of these parameters are defined
in the manual for the relevant CB board, see also function
diagrams, Section 8, Sheets Z110 and Z111)
i015 Code number of board:
1
TB or 1
st
CB
2
2
nd
CB
6
The initialization run for a CB/TB board has not been
completed within 40 s
i015 Code number of board:
1
TB or 1
st
CB
2
2
nd
CB
F081
CB/TB heartbeat error
CB/TB has not incremented the monitoring counter for a period
of 800 ms
Possible causes of fault
♦
CB/TB board is defective
•
CB/TB board is not correctly installed
i015 Code number of board:
1
TB or 1
st
CB
2
2
nd
CB
F082
CB/TB message timeout or error in data exchange
Possible causes of fault
♦
CB/TB PZD message timeout (with fault value 10)
♦
Excessive EMC-related interference
(e.g. due to unprotected contactors, unscreened cables, loose screen connections)
♦
CB/TB board is defective
♦
CB/TB board is not correctly inserted
Fault value (r949 index 001):
r047 Index 002 to 016:
1
Fault in alarm channel from CB to basic unit
i015 Code number of board:
1
TB or 1
st
CB
2
2
nd
CB
2
Fault in alarm channel from TB to basic unit
3
Fault in fault channel from TB to basic unit
5
Fault in parameter job channel from CB to basic unit
i015 Code number of board:
1
TB or 1
st
CB
2
2
nd
CB
6
Fault in parameter response channel from basic unit to
CB
i015 Code number of board:
1
1
st
TB or 1
st
CB
2
2
nd
CB
7
Fault in parameter job channel from TB to basic unit
8
Fault in parameter response channel from basic unit to
TB
10
CB/TB process data failure (message timeout period set
in U722)
i015 Code number of board:
1
TB or 1
st
CB
2
2
nd
CB
11
Fault in parameter job channel from PMU to TB
12
Fault in parameter response channel from TB to PMU
15
Fault in setpoint channel from CB/TB to basic unit
i015 Code number of board:
1
TB or 1
st
CB
2
2
nd
CB
16
Fault in actual value channel from basic unit to CB/TB
i015 Code number of board:
1
TB or 1
st
CB
2
2
nd
CB
10.1.2.14 Fault messages from supplementary boards
F101
to
F147
This group of fault messages is activated by supplementary boards
Please refer to the operating manual of the relevant supplementary board for explanation of the fault messages and fault values
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......