Parameter list
05.05
11-150
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
11.74 Closed-loop control elements
Only active with optional technology software S00
Derivative / delay elements
SW 1.8 and later
FB 270 to FB 279
U550
(2550)
*
S00
(B156)
(B157)
(B158)
Source for input quantity
[SW 1.8 and later]
0 = Connector K0000
1 = Connector K0001
etc.
i001: Input quantity derivative/delay element 1
(FB 270)
i002: Input quantity derivative/delay element 2
(FB 271)
i003: Input quantity derivative/delay element 3
(FB 272)
i004: Input quantity derivative/delay element 4
(FB 273)
i005: Input quantity derivative/delay element 5
(FB 274)
i006: Input quantity derivative/delay element 6
(FB 275)
i007: Input quantity derivative/delay element 7
(FB 276)
i008: Input quantity derivative/delay element 8
(FB 277)
i009: Input quantity derivative/delay element 9
(FB 278)
i010: Input quantity derivative/delay element 10
(FB 279)
All connector
numbers
1
Ind: 10
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
U551
(2551)
*
S00
(B156)
(B157)
(B158)
Source for multiplier for derivative-action time
[SW 1.8 and later]
0 = Connector K0000
1 = Connector K0001
etc.
i001: Multiplier
derivative/delay element 1
(FB 270)
i002: Multiplier
derivative/delay element 2
(FB 271)
I003: Multiplier
derivative/delay element 3
(FB 272)
i004: Multiplier
derivative/delay element 4
(FB 273)
i005: Multiplier
derivative/delay element 5
(FB 274)
i006: Multiplier
derivative/delay element 6
(FB 275)
i007: Multiplier
derivative/delay element 7
(FB 276)
i008: Multiplier
derivative/delay element 8
(FB 277)
i009: Multiplier
derivative/delay element 9
(FB 278)
i010: Multiplier
derivative/delay element 10
(FB 279)
All connector
numbers
1
Ind: 10
FS=1
Type: L2
P052 = 3
P051 = 40
off-line
U552
(2552)
S00
(B156)
(B157)
(B158)
Derivative-action time
[SW 1.8 and later]
i001: Der.-act.time deriv./delay element 1
(FB 270)
i002: Der.-act.time deriv./delay element 2
(FB 271)
i003: Der.-act.time deriv./delay element 3
(FB 272)
i004: Der.-act.time deriv./delay element 4
(FB 273)
i005: Der.-act.time deriv./delay element 5
(FB 274)
i006: Der.-act.time deriv./delay element 7
(FB 276)
i008: Der.-act.time deriv./delay element 8
(FB 277)
i009: Der.-act.time deriv./delay element 9
(FB 278)
i010: Der.-act.time deriv./delay element 10
(FB 279)
0 to 10000
[ms]
1
Ind: 10
FS=100
Type: O2
P052 = 3
P051 = 40
on-line
U553
(2553)
*
S00
(B156)
(B157)
(B158)
Source for multiplier for filtering time
[SW 1.8 and later]
0 = Connector K0000
1 = Connector K0001
etc.
i001: Multiplier
derivative/delay element 1
(FB 270)
i002: Multiplier
derivative/delay element 2
(FB 271)
i003: Multiplier
derivative/delay element 3
(FB 272)
i004: Multiplier
derivative/delay element 4
(FB 273)
i005: Multiplier
derivative/delay element 5
(FB 274)
i006: Multiplier
derivative/delay element 6
(FB 275)
i007: Multiplier
derivative/delay element 7
(FB 276)
i008: Multiplier
derivative/delay element 8
(FB 277)
i009: Multiplier
derivative/delay element 9
(FB 278)
i010: Multiplier
derivative/delay element 10
(FB 279)
All connector
numbers
1
Ind: 10
FS=1
Type: L2
P052 = 3
P051 = 40
off-line
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......