Parameter list
05.05
11-24
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P108
*
FDS
(G161)
Maximum operating speed n3
When the speed-dependent current limitation is in use, the maximum speed
which is defined by the selection of the actual speed source as set in P083,
must be entered in this parameter:
When P083=1 (analog tacho):
Speed at which a tacho voltage as set in P741 is reached
When P083=2 (pulse encoder):
Same value as maximum speed set in P143
When P083=3 (operation without tacho):
Speed at which EMF as set in P115 is reached
1 to 10000
[rev/min]
1rev/min
Ind: 4
FS=5000
Type: O2
P052 = 3
P051 = 40
Offline
P109
*
FDS
(G161)
Control word for speed-dependent current limitation
0
Speed-dependent current limitation is deactivated
1
Speed-dependent current limitation is activated
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P110
FDS
(G162)
(G165)
Armature circuit resistance
This parameter is set automatically during the optimization run for precontrol
and current controller (armature and field) (P051=25).
0.000 to 32.767
[
Ω
]
0.001
Ω
Ind: 4
FS=0.000
Type: O2
P052 = 3
P051 = 40
Online
P111
FDS
(G162)
(G165)
Armature circuit inductance
This parameter is set automatically during the optimization run for precontrol
and current controller (armature and field) (P051=25).
0.000 to 327.67
[mH]
0.01mH
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P112
FDS
(G166)
Field circuit resistance
This parameter is set automatically during the optimization run for precontrol
and current controller (armature and field) (P051=25).
0.0 to 3276.7
[
Ω
]
0.1
Ω
Ind: 4
FS=0.0
Type: O2
P052 = 3
P051 = 40
Online
P113
*
FDS
Continuous current factor torque control / current control
This parameter defines the current to be permitted as a continuous current
by the I
2
t motor monitoring function without activation of alarm message
A037 or fault message F037.
This current is the product of calculation P113 * P100.
0.50 to 2.00
0.01
Ind: 4
FS=1.00
Type: O2
P052 = 3
P051 = 40
Offline
P114
FDS
Thermal time constant of motor
(see Section 9.15)
0.0 I
2
t monitoring deactivated
0.0 to 80.0
[min]
0.1min
Ind: 4
FS=10.0
Type: O2
P052 = 3
P051 = 40
Online
P115
FDS
(G151)
EMF at maximum speed in operation without tachometer
This parameter is used to adjust the speed in cases where the internal
actual EMF value is applied as the actual speed value. P115 defines the
EMF which corresponds to maximum speed as a percentage of P078.001.
1.00 to 140.00
[% of P078.001]
0.01%
Ind: 4
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online
P117
*
FDS
Control word for field characteristic
0
No valid field characteristic has yet been recorded
1
Valid field characteristic (P118 to P139 valid)
The parameter is set automatically during the field-weakening optimization
run (P051=27).
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P118
FDS
(G165)
Rated EMF value
EMF that is reached with a full field (according to parameter P102) and a
speed as set in parameter P119.
The parameter is set automatically during the field-weakening optimization
run (P051=27) and specifies in this case the setpoint EMF in the field-
weakening range.
Note:
As regards the closed-loop field-weakening control, only the ratio between
P118 and P119 is relevant. The EMF setpoint in the field-weakening range
is determined by (P101 – P100 * P110). When the setting in P100, P101 or
P110 is changed subsequently, the field-weakening optimization run need
not be repeated. However, P118 then no longer defines the setpoint EMF in
the field-weakening range.
When the setting in parameter P102 is changed subsequently, the field-
weakening optimization run must be repeated, the same applies if the
maximum speed setting is subsequently re-adjusted.
0 to 2800
[V]
1V
Ind: 4
FS=340
Type: O2
P052 = 3
P051 = 40
Offline
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......