05.05
Parameter list
SIEMENS AG 6RX1700-0AD76
11-169
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U777
(2777)
(Z118)
(Z119)
Offset for analog input on EB2
[SW 1.5 and later]
i001: AI of the first EB2
i002: AI of the second EB2
-100.00 to 100.00
[%]
0.01%
Ind: 2
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
U778
(2778)
*
(Z118)
(Z119)
Mode of signal injection at analog input on EB2
[SW 1.5 and later]
0 = Injection of signal with sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
i001: AI of the first EB2
i002: AI of the second EB2
0 to 3
1
Ind: 2
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
U779
(2779)
*
(Z118)
(Z119)
Source for selection of sign reversal at
[SW 1.5 and later]
analog input on EB2
Selection of binector to control
sign reversal at the analog input
("1" state
= reverse sign)
0 = binector B0000
1 = binector B0001
etc.
i001: AI of the first EB2
i002: AI of the second EB2
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U780
(2780)
(Z118)
(Z119)
Filtering time for analog input on EB2
[SW 1.5 and later]
Note: Hardware filtering of approximately 0.2 ms is applied as standard
i001: AI of the first EB2
i002: AI of the second EB2
0 to 10000
[ms]
1ms
Ind: 2
FS=0
Type: O2
P052 = 3
P051 = 40
Online
U781
(2781)
*
(Z118)
(Z119)
Source for enabling of analog inputs on EB2
[SW 1.5 and later]
Selection of binector to control
enabling of the analog input
("1" state =
enabled)
0 = binector B0000
1 = binector B0001
etc.
i001: AI of the first EB2
i002: AI of the second EB2
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
n782
(2782)
(Z118)
(Z119)
Display of analog input on EB2
[SW 1.5 and later]
i001: AI of the first EB2
i002: AI of the second EB2
-200.0 to 199.99
[%]
0.01%
Ind: 2
Type: I2
P052 = 3
U783
(2783)
*
(Z118)
(Z119)
Source for output value at analog output on EB2
[SW 1.5 and later]
Selection of connector whose value must be output at the analog output
0 = connector K0000
1 = connector K0001
etc.
i001: AO of the first EB2
i002: AO of the second EB2
All connector
numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Online
U784
(2784)
*
(Z118)
(Z119)
Mode of signal injection at analog output on EB2
[SW 1.5 and later]
0 = Injection of signal with sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
i001: AO of the first EB2
i002: AO of the second EB2
0 to 3
1
Ind: 2
FS=0
Type: O2
P052 = 3
P051 = 40
Online
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......