Function descriptions
SIEMENS AG 6RX1700-0AD76
9-11
SIMOREG DC Master Operating Instructions
9.3.4
Operating enable (enable) terminal 38 - control word 1, bit 3
The Enable signal is HIGH active (log."1" state = Enable).
The following operating modes are possible:
P648 = 9:
The control bits in control word 1 are input bit-serially. The operating enable command is
generated from the AND operation between the enable signal from terminal 38 and the
binector selected in P661 (see Section 8, Sheet G180).
P648
≠
9:
The connector selected in P648 is used as control word 1. Bit 3 of this connector is
ANDed with the signal that is generated as for P648=9 to produce the operating enable
signal.
To ensure that the "Operating enable" function can be activated, the conditions defined in the
following diagram must be fulfilled:
&
9
=9
/
1
P648
&
P661.B (1)
B
Control word 1, bit 3
1 = Enable, pulse enable
0 = Pulse disable
Bit 3 of connector selected
as control word in P648
Operating enable
(from terminal 38)
Sequence of operations for enabling operation (if a switch-on command is applied):
1.
Enter the "Enable operation" command
2.
With a positive brake release time (P087), output a "Release holding or operating
brake" signal (binector B0250 = 1) and wait for P087 to run down in operating state o1.0,
with a negative brake release time (P087 negative), go to step 3 immediately, brake
remains closed (binector B0250 = 0)
3.
Ramp-function generator, n and I controllers are enabled
4.
Converter reaches operating state I, II or – –
5.
When a negative brake release time (P087) has run down, output signal "Release holding or
operating brake" (binector B0250 = 1).
Sequence of operations for cancellation of operating enable:
1.
Cancel "Enable operation" command
2.
Disable ramp-function generator, n and I controllers
3. Enter
I
set
= 0
4.
The pulses are disabled when I = 0
5.
Output signal "Close operating brake" (binector B0250 = 0, when P080 = 2)
6.
The converter reaches operating state 0.10 or higher
7.
Drive coasts to a standstill (or is braked by the operating brake)
8.
When n < n
min
(P370, P371) is reached, the signal "Close holding brake" is output (binector
B0250, when P080 = 1)
9.4 Ramp-function
generator
See also Section 8, Sheet G136
NOTICE
The following conditions must be fulfilled for the ramp-function generator to work:
−
Ramp-function generator enable = 1
(control word 1.bit 4 = 1)
−
Enable setpoint = 1
(control word 1.bit 6 = 1)
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......