
Parameter list
05.05
11-12
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
11.3
Access authorization levels
P051
*
Key parameters
0
No access authorization
6
Do not set (for use by DriveMonitor)
7
Do not set (for use by DriveMonitor)
9
Do not set (for use by DriveMonitor)
21
Restore factory settings
All parameters are reset to their defaults (factory settings).
Parameter P051 is then automatically reset to factory setting
"40".
22
Execute internal offset compensation (see Section 7.4)
25
Optimization run for precontrol and current controller (armature
and field) (see Section 7.5)
26
Optimization run for speed controller (see Section 7.5)
27
Optimization run for field weakening (see Section 7.5)
28
Optimization run for compensation of friction and moment of
inertia (see Section 7.5)
29
Optimization run for the speed controller with an oscillating
mechanical system (see Section 7.5)
40
Access authorization to parameter values for authorized service
personnel
see column on left
Ind: None
FS=40
Type: O2
P052 = 3
P051
≥
0
Online
P052
*
Selection of display parameters
0
0 Display only parameters that are not set to original factory
settings
1
Display only parameters for simple applications
3
Display all parameters used
0, 1, 3
Ind: None
FS=3
Type: O2
P052 = 3
P051
≥
0
Online
P053
*
Control word for the permanent memory
[SW 1.7 and later]
Disabling or enabling write accesses to the permanent memory
i001: Disabling or enabling write accesses to the parameter memory
0 Only save parameter P053 in the permanent memory;
parameter changes are active immediately but the changed
values are only stored temporarily and are lost when the
electronics supply voltage is switched off
1 Save all parameter values in the permanent memory
i002: Disabling or enabling write accesses to the memory of the
nonvolatile process data
0 Do not save nonvolatile process data in the permanent
memory
1 Save all nonvolatile process data in the permanent memory
If the nonvolatile process data are not stored (P053.002=0),
data are lost when the electronics supply of the SIMOREG DC
Master is switched off, i.e. they have the value 0 after the
electronics supply is switched on again:
K0240: Setpoint of the motor potentiometer
K0309: Motor heating
K0310: Thyristor heating
K9195: Output of the 1st tracking/storage element
K9196: Output of the 2nd tracking/storage element
0 to 1
1
Ind: 2
FS=1
Type: O2
P052 = 3
P051 = 0
on-line
P054
OP1S – Background lighting
0 ON
continuously
1
ON when panel is in use
0, 1
Ind: None
FS=0
Type: O2
P052 = 3
P051
≥
0
Online
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......