Parameter list
05.05
11-82
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P778
(G112)
Delay for output value at binary output 4
The logic level at the binary selectable output changes only if the internal
signal level remains constant for the set delay period (internal signal level
changes which do not last as long as this delay period are not switched
through to the output)
0 to 10000
[ms]
1ms
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
11.41 Configuration of serial interfaces on basic converter
G-SST 1 (RS485 / RS232 on X300)
(see also Section 8, Sheet G170 and Section 9)
P780
*
(G170)
Selection of protocol for G-SST1 basic converter interface
0
Setting has no function
2 USS
protocol
8
for factory purposes
9
For internal factory test purposes
0, 2, 8, 9
1
Ind: None
FS=2
Type: O2
P052 = 3
P051 = 40
Offline
P781
*
(G170)
Number of process data for G-SST1
When P780 = 0 or 9 is selected: Parameter is irrelevant
When USS protocol (P780=2) is selected: Number of
PZD elements
0
No process data are expected or sent in the USS protocol
1...16 Number of process data words in USS protocol (same number
applies to transmission and receipt)
The received PZD elements (1 to max. 16) are available at
connectors (K2001 to K2016) and, in some cases, bit-serially at
binectors for "internal wiring" purposes.
The PZD elements to be transmitted (1 to max. 16) are selected
in parameters P784.01 to P784.16.
0 to 16
1
Ind: None
FS=2
Type: O2
P052 = 3
P051 = 40
Offline
P782
*
(G170)
Length of parameter jobs for G-SST1
This parameter is effective only when P780=2 (USS protocol).
0
No PKW data are expected or sent in the USS protocol.
3, 4
3 or 4 PKW data words are expected in the USS protocol and 3
or 4 PKW data words are also sent (for transmission of
parameter values).
127
Number of PKWs is determined by the telegram length
0, 3, 4, 127
1
Ind: None
FS=127
Type: O2
P052 = 3
P051 = 40
Offline
P783
*
(G170)
Baud rate for G-SST1
1 300
baud
2 600
baud
3 1200
baud
4 2400
baud
5 4800
baud
6 9600
baud
7 19200
baud
8 38400
baud
9 56700
baud
11 93750
baud
13 187500
baud
1 to 13
1
Ind: None
FS=6
Type: O2
P052 = 3
P051 = 40
Offline
P784
*
(G170)
Source for transmit data for G-SST1
Selection of connectors to be transferred as transmit data to the USS
master via USS interface 1.
i001: Selection for word 1
i002: Selection for word 2
...
i016: Selection for word 16
Applicable settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 16
FS=
i001: 32
i002: 167
i003: 0
i004: 33
i005-i016: 0
Type: L2
P052 = 3
P051 = 40
Offline
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......