05.05
Start-Up
SIEMENS AG 6RX1700-0AD76
7-49
SIMOREG DC Master Operating Instructions
The consistency of a block of data words is guaranteed within a DeviceNet I/O message
connection even in cases where more than 4 PZD words are used and the transmission data is
distributed among several telegrams. The data are not transferred from the CBD to the drive until
all data words have been received.
PKW object (parameter data)
The manufacturer-specific PKW object (class 100) is used to read and modify parameters of the
drive or a technology board by means of the DeviceNet master (PKW = parameter identifier value).
Explicit messaging mode is used for this purpose.
Only two instances are implemented for the PKW object: Instance 0 permits access to class
attributes and instance 1 (always set to "1") access to all parameter numbers (see DeviceNet
objects below).
Apart from the protocol header and trailer specific to DeviceNet, the structure of a telegram is
follows:
Parameter identifier
PKE
Parameter index
IND
Parameter value1
PWE1
Parameter value2
PWE2
For details about this telegram area, see also Section 7.7.9, Structure of request/response
telegrams. The useful data area of PROFIBUS, CAN Bus and DeviceNet telegrams is structured
identically.
DeviceNet GET Single
This object is used to read parameter values and 9 bytes in length.
Byte DeviceNet
identification
1
[FRAG] [XID] [SRC/DST MAC ID]
2 [R/R]
[Service]
0x0E
[Get_Attribute_Single]
3
Class
100
[PKW object] manufacturer-specific
4
Instance
1
[Instance number] always set to 1
5
Attribute
1
[Attribute number] always set to 1
6
Parameter ID, L byte
7
PKE
Parameter ID, H byte
8
Parameter index, L byte
9
IND
Parameter index, H byte
DeviceNet SET Single
This object is used to modify parameter values and 14 bytes in length
Byte DeviceNet
identification
1
[FRAG] [XID] [SRC/DST MAC ID]
2 [Fragmentation
Protocol]
3 [R/R]
[Service]
0x10
[Set_Attribute_Single]
4
Class
100
[PKW object] manufacturer-specific
5
Instance
1
[Instance number] always set to 1
6
Attribute
1
[Attribute number] always set to 1
7
Parameter ID, L byte
8
PKE
Parameter ID, H byte
9
Parameter index, L byte
10
IND
Parameter index, H byte
11
Parameter value, L word, L byte
12
PWE1
Parameter value, L word, H byte
13
Parameter value, H word, L byte
14
PWE2
Parameter value, H word, H byte
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......