05.05
Parameter list
SIEMENS AG 6RX1700-0AD76
11-53
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P471
*
BDS
(G126)
Source for manual/automatic switchover
Selection of binector to control
"Manual/automatic switchover"
("0" state = manual).
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P472
*
BDS
(G126)
Source for set motorized potentiometer
Selection of binector to control
"Set motorized potentiometer"
("0" to "1" transition = set motorized potentiometer).
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P473
*
FDS
(G126)
Storage of output value
0
No storage of output value:
The output is set to 0 in all operating states of >o5.
The starting point after ON is determined by P467 (MOP starting
value).
1
Non-volatile storage of output value:
The output value remains stored in all operating states and after
voltage disconnection or failure. The last value stored is output
again after voltage recovery/reconnection.
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
11.26 Oscillation
Function:
Parameters P480 to P483 define the waveshape of a rectangular signal (oscillation setpoint K0203). The value set in P480 determines the
signal level for the time period set in P481 and the value set in P482 the signal level for the time period set in P483.
Oscillation: Selected in P485. The free-running rectangular signal is switched through to the output K0208.
P480
FDS
(G128)
Oscillation setpoint 1
-199.9 to 199.9
[%]
0.1% of maximum
speed
Ind: 4
FS=0,5
Type: I2
P052 = 3
P051 = 40
Online
P481
FDS
(G128)
Oscillation time 1
0.1 to 300.0
[s]
0.1s
Ind: 4
FS=0.1
Type: O2
P052 = 3
P051 = 40
Online
P482
FDS
(G128)
Oscillation setpoint 2
-199.9 to 199.9
[%]
0.1% of maximum
speed
Ind: 4
FS=-0,4
Type: I2
P052 = 3
P051 = 40
Online
P483
FDS
(G128)
Oscillation time 2
0.1 to 300.0
[s]
0.1s
Ind: 4
FS=0.1
Type: O2
P052 = 3
P051 = 40
Online
P484
*
FDS
(G128)
Source for standard setpoint
Selection of connector to be injected as the output value when the
"Oscillation" function is not selected
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=209
Type: L2
P052 = 3
P051 = 40
Offline
P485
*
BDS
(G128)
Source for oscillation selection
Selection of binector to control activation of the "Oscillation" function
(log. "1" state = oscillation active)
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......