Start-Up
05.05
7-50
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
DeviceNet Response
This object is used to respond to requests of the above type and 8 bytes in length.
Byte DeviceNet
identification
1
[FRAG] [XID] [SRC/DST MAC ID]
2 [R/R]
[Service]
0x8E
[Get/Set_Attribute_Single]
0x90
3
Parameter ID, L byte
4
PKE
Parameter ID, H byte
5
Parameter value, L word, L byte
6
PWE1
Parameter value, L word, H byte
7
Parameter value, H word, L byte
8
PWE2
Parameter value, H word, H byte
Examples
Read parameter P101.004 using GET Single (for details in the shaded data area, see also Section
7, Starting up PROFIBUS boards):
Byte DeviceNet
identification
1
[FRAG] [XID] [SRC/DST MAC ID]
2 [R/R]
[Service]
0x0E
[Get_Attribute_Single]
3
Class
100
[PKW object] manufacturer-specific
4
Instance
1
[Instance number] always set to 1
5
Attribute
1
[Attribute number] always set to 1
6
0x65
Parameter ID, L byte
7
PKE
0x60
Parameter ID, H byte
8
4
Parameter index, L byte
9
IND
0
Parameter index, H byte
Request identifier = 0x6065 (request parameter value (array) P101), Index = 0004h = 4d
Response by SIMOREG:
Byte DeviceNet
identification
1
[FRAG] [XID] [SRC/DST MAC ID]
2 [R/R]
[Service]
0x8E
[Get_Attribute_Single]
3
0x65
Parameter ID, L byte
4
PKE
0x40
Parameter ID, H byte
5
0x90
Parameter value, L word, L byte
6
PWE1
0x01
Parameter value, L word, H byte
7
0x00
Parameter value, H word, L byte
8
PWE2
0x00
Parameter value, H word, H byte
Response identifier = 0x4065, value of P101.004 = 0190h = 400d (PWE2 remains unused because
it is not a double word parameter)
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......