Parameter list
05.05
11-46
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
n < ncomp. signal
P373
FDS
(G187)
Speed threshold ncomp.
Speed threshold for n < ncomp. signal
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online
P374
FDS
(G187)
Hysteresis for < ncomp. signal (n < ncomp. signal)
This value is added to the response threshold if n < ncomp.
is active.
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=3.00
Type: O2
P052 = 3
P051 = 40
Online
P375
FDS
(G187)
OFF delay for n < ncomp. signal
0.0 to 100.0
[s]
0.1s
Ind: 4
FS=3.0
Type: O2
P052 = 3
P051 = 40
Online
Setpoint/actual value deviation 2
P376
FDS
(G187)
Permissible setpoint/actual value deviation 2
[SW 1.9 and later]
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FD=3.00
Type: O2
P052 = 3
P051 = 40
on-line
P377
FDS
(G187)
Hysteresis for setpoint/actual value deviation 2 signal
[SW 1.9 and later]
This value is added to the response threshold if a setpoint/actual value
deviation signal is active
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=1.00
Type: O2
P052 = 3
P051 = 40
on-line
P378
FDS
(G187)
Response delay for setpoint/actual value deviation signal 2
[SW 1.9 and later]
0.0 to 100.0
[s]
0.1s
Ind: 4
FS=3.0
Type: O2
P052 = 3
P051 = 40
on-line
Overspeed
P380
FDS
(G188)
Maximum speed in positive direction of rotation
0.0 to 199.9
[%]
0.1% of maximum
speed
Ind: 4
FS=120.0
Type: O2
P052 = 3
P051 = 40
Online
P381
FDS
(G188)
Maximum speed in negative direction of rotation
-199.9 to 0.0
[%]
0.1% of maximum
speed
Ind: 4
FS=-120.0
Type: I2
P052 = 3
P051 = 40
Online
Setpoint/actual value deviation 1
P388
FDS
(G187)
Permissible deviation between setpoint and actual value 1
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=3.00
Type: O2
P052 = 3
P051 = 40
Online
P389
FDS
(G187)
Hysteresis for setpoint/actual value deviation signal 1
This value is added to the response threshold if a setpoint/actual value
deviation signal is active
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=1.00
Type: O2
P052 = 3
P051 = 40
Online
P390
FDS
(G187)
Response delay for setpoint/actual value deviation signal 1
0.0 to 100.0
[s]
0.1s
Ind: 4
FS=3.0
Type: O2
P052 = 3
P051 = 40
Online
If < If min signal
P394
FDS
(G188)
Field current threshold If min
Field current threshold for If < If min limit-value monitor.
Note:
This threshold affects the sequence of control operations for the "Direction
of rotation reversal using field reversal" and "Braking with field reversal"
functions (see Section 9).
The If < If min signal is connected to binector B0215, the actual value at
field current controller input K0265 is applied as If.
B0215 = 0 when K0265 > threshold set in P394
B0215 = 1 when K0265 < threshold set in P394 + hysteresis set in P395
0
→
1 transition takes place when K0265 < P394
1
→
0 transition takes place when K0265 > P394 + P395
0.00 to 199.99
[%]
0.01% of converter
rated field DC
current (r073.i02)
Ind: 4
FS=3.00
Type: O2
P052 = 3
P051 = 40
Online
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......