05.05
Parameter list
SIEMENS AG 6RX1700-0AD76
11-103
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U049
(2049)
OP1S operating display
[SW 1.9 and later]
Function parameter for selecting parameters whose values must be
included in the operating display of the optional
OP1S convenience operator panel.
i001: 1
st
line on left
i002: 1
st
line on right
i003: 2
nd
line (actual value), visualization parameter only
i004: 3
rd
line (setpoint)
i005: 4
th
line
0 to 3999
1
Ind:5
FS=
i001: 19
i002: 38
i003: 25
i004: 28
i005: 59
Type: O2
P052 = 3
P051 =40
on-line
Connector type converters
(only active with optional technology software S00)
2 connectors are converted into one double word connector.
U098
(2098)
*
S00
(B151)
Operands for 1
st
connector type converter
(result = KK9498)
FB 298
Operands for 2
nd
connector type converter
(result = KK9499)
FB 299
[SW 1.9 and later]
i001: Source for the low word of output connector
KK9498
i002: Source for the high word of output connector
KK9498
i003: Source for the low word of output connector KK9499
i004: Source for the high word of output connector
KK9499
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
11.56 Settable fixed values
Only active with optional technology software S00
U099
(2099)
S00
(B110)
Fixed value
[SW 1.8 and later]
The values set in Index .001 to .100 are connected to connectors K9501 to
K9600
-199.99 to 199.99
[%]
0.01%
Ind: 100
FS=0.00
Type: I2
P052 = 3
P051 = 40
on-line
11.57 Activation of fault messages and alarm messages
Only active with optional technology software S00
U100
(2100)
*
S00
(B115)
Source for the activation of F023 and F019
FB 2, FB 286
Selection of the binectors that activate fault messages F023 or F019 on log.
"1"
0 = Binector B0000
1 = Binector B0001
etc.
Up to SW 1.7: F023 (without fault value) if binector = 1 (FB 2)
SW 1.8 and later:
i001: F023 with fault value 1 (FB 2)
i002: F023 with fault value 2
i003: F023 with fault value 3
i004: F023 with fault value 4
i005: F019 with fault value 1 (FB 286)
i006: F019 with fault value 2
i007: F019 with fault value 3
i008: F019 with fault value 4
All binector numbers
1
Ind: 8
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......