05.05
Faults / Alarms
SIEMENS AG 6RX1700-0AD76
10-21
SIMOREG DC Master Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
10.1.2.12 Internal faults
F062
Fault in parameter memory
(active in all operating states)
Software monitoring of correct functioning of the EEPROM module (non-volatile memory) on the A7009 board.
The EEPROM values contains all data which must be protected in the case of a power failure (i.e. parameter values and process
data which must remain stored during power failures).
The following are monitored:
♦
Connection between the A7001 electronics board and the EEPROM on the A7009 backplane wiring assembly
♦
Whether the parameter values stored on the EEPROM are within the permissible value range
♦
Whether data are being correctly stored on the EEPROM. For this purpose, values are read and checked for correctness
after they are transferred to the module
♦
Whether the checksum of the non-volatile process data in the EEPROM is correct
Possible causes for all fault types:
Excessive EMC-related interference is present (e.g. due to unprotected contactors, unscreened cables, loose shield connections)
Fault value:
r047 Index 002 to 016:
1
Connection to EEPROM is faulty
Possible fault causes
•
A7001 electronics board is defective
•
A7009 backplane wiring assembly is defective
•
Plug-in connection X109 is defective
2
Parameter value is outside permissible value range
Possible fault causes
•
“Restore to default value” has never been executed
with this software (e.g. after software replacement)
•
A7009 backplane wiring assembly is defective
Possible remedy:
•
Acknowledge fault, execute “Restore to default value”
and start up the drive again
i002 Number of faulty parameter
i003 Index of faulty parameter
i004 Faulty parameter value
3
Parameter value cannot be stored on EEPROM
Possible fault causes
•
A7001 electronics board is defective
•
A7009 backplane wiring assembly is defective
•
Plug-in connection X109 is defective
i002 Address of fault memory location
i003 Faulty value in EEPROM
i004 Correct parameter value
11
Checksum of non-volatile data (part 1)
is not correct
12
Checksum of non-volatile data (part 2)
is not correct
13
Checksum of non-volatile data (part 3)
is not correct
20
Checksum of configuring table of parameter values is not
correct
Possible fault causes
•
Defective
EEPROM
•
“Restore to default value” has never been executed
with this software (e.g. after software replacement)
Possible remedy:
•
Acknowledge fault, execute “Restore to default value”
and start up the drive again! Check interference
suppression measures and improve if necessary.
i002 Calculate checksum
i003 Checksum found in EEPROM
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......