05.05
Parameter list
SIEMENS AG 6RX1700-0AD76
11-73
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P684
*
BDS
(G181)
Source for control word 2, bit24
(0=n controller speed droop disabled, 1=enabled)
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P685
*
BDS
(G181)
Source for control word 2, bit25
(0=n controller disabled, 1=n controller enabled)
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P686
*
BDS
(G181)
Source for control word 2, bit26
(0=external fault 2, 1=no external fault 2)
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P687
*
BDS
(G181)
Source for control word 2, bit27
(0=master drive, speed control, 1=slave drive, torque control)
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P688
*
BDS
(G181)
Source for control word 2, bit28
(0=external alarm 1, 1=no external alarm 1)
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P689
*
BDS
(G181)
Source for control word 2, bit29
(0=external alarm 2, 1=no external alarm 2)
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P690
*
(G181)
Source for control word 2, bit30
(0=select Bico data set 1, 1=select Bico data set 2)
All binector numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P691
*
BDS
(G181)
Source for control word 2, Bit31
[SW 1.8 and later]
Main contactor checkback signal:
(0 = main contactor dropped out, 1 = main contactor picked up)
This control input is intended as a means of looping an auxiliary contact of
the main contactor into the device control.
During the Power ON routine, this signal must switch to "1" within the time
period set in P095. If it does not, or it disappears during operation, fault
message F004 with fault value 6 is activated.
P691 = 0: Bit 31 of control word 2 is inoperative.
(This setting of P691 is always active, regardless of whether
control word 2 is input in word mode [P649 = 9] or bit mode
[P649 <> 9])
P691 = 1: Bit 31 of control word 2 is inoperative.
(This setting of P691 is active only when control word 2 is input
in bit mode, i.e. when P649 <> 9)
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
11.37 Further configuring measures
P692
*
BDS
(G166)
Source for selection of injection of standstill field
Selection of binector to control
injection of the standstill field
("0" state =
inject standstill field)
Note:
The delay time set in P258 is not effective when this function is
active.
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P693
*
BDS
(G165)
Source for selection of enabling command for EMF controller
Selection of binector which is to control
enabling of the EMF controller
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......