05.05
Parameter list
SIEMENS AG 6RX1700-0AD76
11-141
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U472
(2472)
*
S00
(B216)
Source for input signals for binary signal selector switch 3
FB 252
(output = B9484)
As for U470
All binector numbers
1
Ind: 3
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U473
(2473)
*
S00
(B216)
Source for input signals for binary signal selector switch 4
FB 253
(output = B9485)
As for U470
All binector numbers
1
Ind: 3
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U474
(2474)
*
S00
(B216)
Source for input signals for binary signal selector switch 5
FB 254
(output = B9486)
As for U470
All binector numbers
1
Ind: 3
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
11.70 Technology
controller
Only active with optional technology software S00
Technology controller: Actual value
U480
(2480)
*
S00
(B170)
Source for actual value
FB 114
Selection of connectors to be added as the actual value
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U481
(2481)
S00
FDS
(B170)
Filter time for actual value
FB 114
0.00 to 600.00
[s]
0.01
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
U482
(2482)
S00
FDS
(B170)
Derivative-action time for actual value (D component)
FB 114
0.000 = D component deactivated
See also U483
0.000 to 30.000
[s]
0.001
Ind: 4
FS=0.000
Type: O2
P052 = 3
P051 = 40
Online
U483
(2483)
*
S00
FDS
(B170)
Factor for derivative-action time
FB 114
0
Derivative-action time = U482 * 1
1
Derivative-action time = U482 * 1000
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
Technology controller: Setpoint
U484
(2484)
*
S00
(B170)
Source for setpoint
FB 114
Selection of connectors to be added as the setpoint
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U485
(2485)
S00
FDS
(B170)
Injectable additional setpoint
FB 114
This parameter setting is added to the setpoint when the binector selected
in U486 changes to the log. "1" state
-200.00 to 199.99
[%]
0.01
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
U486
(2486)
*
S00
(B170)
Source for control bit for injection of additional setpoint
FB 114
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U487
(2487)
S00
FDS
(B170)
Filter time for setpoint
FB 114
0.00 to 600.00
[s]
0.01
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......