9.18.1 Direction of rotation reversal using field reversal
This function is controlled by the binector selected in P580.
The "Direction of rotation reversal using field reversal" has a switch function and defines the field
direction and, if a positive speed setpoint is applied, also the direction of rotation.
Level:
0
Positive field direction is selected
(”Close field contactor 1” (B0260) = 1, ”Close field contactor 2”
(B0261) = 0)
1
Negative field direction is selected
(”Close field contactor 1” (B0260) = 0, ” Close field contactor 2”
(B0261) = 1)
Changing the logic level of the binector controlling the "Direction of rotation reversal using field
reversal" function initiates an internal sequence which brakes the motor and accelerates it in the
opposite direction.
While the field reversal process is in progress, the logic level of the controlling binector is irrelevant,
i.e. once the function has commenced, it is completed without interruption. Only on completion is
another check made to establish whether the logic level of the controlling binector actually coincides
with the currently selected field direction.
Note:
Only positive speed setpoints are meaningful.
Sequence of control operations when "Direction of rotation reversal using field reversal" is
applied:
1.
Drive is rotating in rotational direction 1 (or is at standstill)
2.
Logic level of binector controlling the "Direction of rotation reversal using field reversal" changes
3.
Internal field reversal process takes place (only if a braking operation has not already been
activated by pushbutton function "Braking with field reversal"):
3.1
Wait for armature current I
A
= 0 and then armature pulse disable
(drive then dwells in operating state
≥
o1.4)
3.2
Disable field firing pulses (also causes K0268=0)
3.3
Wait for I
field
(K0265)
< I
field min
(P394)
3.4
Waiting time according to P092.i001 (0.0 to 10.0 s, factory setting 3.0 s)
3.5
Open current field contactor (B0260 = 0 or B0261 = 0)
3.6
Waiting time according to P092.i002 (0,0 to 10,0 s, factory setting 0,2 s)
3.7
Close new field contactor (B0261 = 1 or B0260 = 1)
3.8
Reverse polarity of actual speed value (except when P083 = 3 ... EMF as actual speed
value)
3.9
Waiting time according to P092.i003 (0,0 to 10,0 s, factory setting 0,1 s)
3.10 Enable field firing pulses
3.11 Wait for I
field
(K0265) > I
field set
(K0268)*P398/100%
3.12 Waiting time according to P092.i004 (0,0 to 10,0 s, factory setting 3,0 s)
3.13 Enable armature firing pulses
(It is possible to exit operating mode o1.4)
4.
Drive brakes and then accelerates in rotational direction 2 (or remains at standstill)
Note:
If the actual speed value polarity is reversed internally as a result of field reversal, P083 (but not
P083=3) is supplied with inverted signal values (see Section 8, Sheet G152). When the ramp-function
generator is in use, it is advisable to set P228=0 (no speed controller setpoint filtering). Otherwise,
initial braking along the current limit may occur in connection with the actual speed value polarity
reversal and setting of the ramp-function generator output (to (reversed) actual speed value (or to
value set in P639) in operating state o1.4).
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......