Parameter list
05.05
11-92
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P817
(G173)
Peer-to-peer 2: Source for data transmission enabling command
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P818
(G174)
Peer-to-peer 3: Source for data reception enabling command
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P819
(G174)
Peer-to-peer 3: Source for data transmission enabling command
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
11.42 Deactivation
of
monitoring functions
WARNING
If monitoring functions are deactivated, there may be a risk to the safety of operating personnel or of
substantial property damage if a fault or error actually occurs!
P820
*
Deactivation of fault messages
The numbers of all fault messages to be deactivated must be entered in this
parameter. Fault numbers can be entered in any order. 0 must be entered
for any unused indices of the parameter.
Factory setting:
i001 = 7
(overvoltage)
i002 = 18
(short circuit at binary outputs)
i003 = 31
(monitoring of speed controller)
i004 = 35
(drive blocked)
i005 = 36
(armature current cannot flow)
i006 = 37
(I
2
t motor monitoring function has responded)
i007 to i099 = 0
0 to 147
1
Ind: 99
FS=
see column
on left
Type: O2
P052 = 3
P051 = 40
Online
P821
*
Deactivation of alarms
The numbers of all alarm messages to be deactivated must be entered in
this parameter. Alarm numbers can be entered in any order. 0 must be
entered for any unused indices of the parameter.
0 to 147
1
Ind: 99
FS= 0
Type: O2
P052 = 3
P051 = 40
Online
11.43 Compensation
values
r824
A7006 compensation values
These data contain compensation values for the analog section of
electronics board A7006
0 to 65535
1
Ind: 10
Type: O2
P052 = 3
P825
Offset compensation for actual field current channel
These data contain compensation values for the actual field current sensing
function. They are automatically set during "Restore factory settings"
(P051=21) and during the automatic offset compensation run (P051=22).
13000 to 25000
1
Ind: 3
FS=19139
Type: O2
P052 = 3
P051 = 40
Online
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......