05.05
Parameter list
SIEMENS AG 6RX1700-0AD76
11-181
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
11.99 Enabling of technology software in basic unit, S00 option
("freely assignable function blocks")
The S00 technology option can only be utilized on SIMOREG DC Master converters on which this option has been enabled by a proper
PIN number. The software remains enabled after software updates, i.e. it need not be enabled again after new software has been
installed.
Permanent enabling of S00 technology option (subject to charge):
Please proceed as follows if you wish to enable the S00 technology option:
1. Find out the serial number of your SIMOREG DC Master unit (e.g. "Q6K31253320005"):
•
The serial number is specified on the delivery note
•
The serial number is printed on the rating plate of the SIMOREG DC Master
•
The serial number can be displayed in parameter r069 on the OP1S
2. Find out the PIN number (a number between 2001 and 65535) which matches the converter serial number:
•
If you have ordered the SIMOREG Master with S00 option, you will find the PIN number printed on a sticker on the unit and
specified on the delivery note.
•
If not, please contact your local Siemens sales office to obtain the correct PIN number.
3. Enter the PIN number in parameter U977 and complete your entry by pressing button <P>. This parameter is automatically reset to
0 after the entry is made. Enter the PIN number with care as you only have five attempts.
4. Technology option S00 is now enabled, which can be verified in n978 = 2000.
Technology option S00 can be disabled by entering U997 = PIN - 1 (e.g. for test purposes). Parameter n978 then displays 500. The option
is enabled again by entering U977 = PIN.
Temporary enabling of S00 technology option (free of charge):
The S00 technology option can be enabled
once
, free of charge, on all converters for 500 hours of use by means of a special PIN
number. This 500-hour period can be used for test purposes or for the operation of replacement units which have been ordered without
the S00 option (i.e. to cover the period until a PIN number for permanent enabling is obtained).
The 500 hours are counted by the hours run counter (r048) , i.e. only the time that the drive is actually switched on is counted. When the
500-hour period has expired, the S00 option is disabled automatically if the PIN number for permanent enabling has not been entered in
the meantime.
The special PIN number is: U977 =
1500
(identical number for all units)
Temporary enabling of the option can be interrupted with PIN U977 =
500
. The remaining time credit remains valid for the next period of
use with the temporarily enabling PIN number.
Alarm
A059
is output if the time credit is less than 50 hours and the S00 technology option is temporarily enabled.
Fault message
F059
is displayed if the time credit of 500 hours has run out and the S00 option is still temporarily enabled.
System response when S00 technology option is not enabled:
The connectors and binectors associated with freely assignable function blocks are not updated (they are set to 0 when the electronics
voltage is connected; when the time credit for temporary enabling has run out, they remain frozen at the last recorded values until the
electronics voltage is disconnected again).
U977
(2977)
*
S00
PIN number for S00 option
This parameter is automatically reset to "0" after entry of the PIN number.
Take care to enter the PIN number correctly. You are only allowed up to 5
attempts!
0 to 65535
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
n978
(2978)
S00
"S00 enabled" display
0
The optional S00 technology software is disabled
The time credit for temporary enabling has run out
xxx
The optional S00 technology software is not enabled.
xxx = number of credit hours which are still available for use
under temporary enabling PIN number
1xxx
The optional SOO technology software is temporarily enabled.
xxx = number of credit hours still available
2000 The optional S00 technology software is permanently enabled.
see column on left
Ind: None
Type: O2
P052 = 3
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......