Parameter list
05.05
11-172
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U807
(2807)
(G195)
Telegram failure time on paralleling interface
0
No time monitoring
0.001...65.000 Permissible time interval between two data exchange
operations before a fault message is output.
Fault message F014 is displayed if no data are exchanged with the parallel-
connected converter within this delay period.
The monitoring function is implemented within a 20 ms cycle. For this
reason, only setting values which constitute a multiple of 20 ms are
meaningful.
Note:
The telegram monitoring function is active
•
from the receipt of the first error-free telegram after connection of the
electronics power supply
•
from the receipt of the first error-free telegram after the telegram monitor
has responded (i.e. monitoring timeout).
0.000 to 65.000
[s]
0.001s
Ind: None
FS=0.100
Type: O2
P052 = 3
P051 = 40
Online
U808
(2808)
*
(G195)
Source for triggering of message F014
Selection of binector which must trigger message F014 when it switches to
log. "1"
6040 = binector B6040
6041 = binector B6041
6040, 6041
Ind: None
FS=6040
Type: L2
P052 = 3
P051 = 40
Offline
n809
(2809)
(G195)
Diagnostic information for paralleling interface
i001 to i009 = Free-running counter, overflow at 65535
i001: Number of error-free telegrams
i002: Number of errored telegrams
i003: Transmit Error Counter
i004: Receive Error Counter
i005: Phase Error Counter
i006: Baud rate Error Counter
i007: Bad BCC Counter
i008: Timeout
Counter
i009: Number of telegrams with unknown identifier
0 to 65535
Ind: 9
Type: O2
P052
≥
0
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......