Parameter list
05.05
11-122
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U262
(2262)
*
S00
(B155)
Source for control signals
FB 100
i001
Source for "Stop integrator" signal
(integrator is stopped when binector reaches log. "1" state)
i002
Source for "Set integrator" signal
(when binector reaches log. "1" state, the integrator is set to the
value entered in parameter U263)
Settings:
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U263
(2263)
*
S00
(B155)
Source for setting value
FB 100
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
Integrator 2
(output = K9221)
U264
(2264)
*
S00
(B155)
Source for input quantity
FB 101
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U265
(2265)
S00
(B155)
Integral-action time
FB 101
10 to 65000
[ms]
1
Ind: None
FS=10
Type: O2
P052 = 3
P051 = 40
Online
U266
(2266)
*
S00
(B155)
Source for control signals
FB 101
i001
Source for "Stop integrator" signal
(integrator is stopped when binector reaches log. "1" state)
i002
Source for "Set integrator" signal
(when binector reaches log. "1" state, the integrator is set to the
value entered in parameter U267)
Settings:
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U267
(2267)
*
S00
(B155)
Source for setting value
FB 101
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
Integrator 3
(output = K9222)
U268
(2268)
*
S00
(B155)
Source for input quantity
FB 102
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U269
(2269)
S00
(B155)
Integral-action time
FB 102
10 to 65000
[ms]
1
Ind: None
FS=10
Type: O2
P052 = 3
P051 = 40
Online
U270
(2270)
*
S00
(B155)
Source for control signals
FB 102
i001
Source for "Stop integrator" signal
(integrator is stopped when binector reaches log. "1" state)
i002
Source for "Set integrator" signal
(when binector reaches log. "1" state, the integrator is set to the
value entered in parameter U271)
Settings:
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......