05.05
Connections
Siemens AG 6RX1700-0AD76
6-69
SIMOREG DC Master Operating Instructions
Serial interface 2 RS485
(G-SST2)
Module C98043-A7001 (CUD1)
Function Terminal
X172
Connection values/Remarks
TX+
56
RS485, 4-wire send cable, positive differential output
TX-
57
RS485, 4-wire send cable, negative differential output
RX+/TX+
58
RS485, 4-wire receive cable, positive differential input,
2-wire send/receive cable, positive differential input
RX-/TX-
59
RS485, 4-wire receive cable, negative differential input,
2-wire send/receive cable, negative differential input
M 60
Ground
Cable length: For transmission rate =187.5kBd
⇒
600m
For transmission rate
≤
93.75kBd
⇒
1200m
The following must be observed: DIN 19245 Part 1
The potential difference between the data reference potentials M of all interfaces must not
exceed -7V / +12V. If this cannot be guaranteed, then equipotential bonding must be
provided.
Activation of interface 1 or 2:
– Set the baud rate in parameter P783 or P793.
– Set the protocol in parameter P780 or P790.
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......