05.05
Faults / Alarms
SIEMENS AG 6RX1700-0AD76
10-5
SIMOREG DC Master Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
Fault value:
r047 Index 002 to 016:
1
Undervoltage has occurred
i002 Number of phase that has activated fault message
0 ... Phase
UV
1 ... Phase
VW
2 ... Phase
WU
3 ... Phase
field
i003 Incorrect voltage value (normalized to 16384)
4
Undervoltage persists for longer than time set in
parameter P086 (if this is set to >0)
-
F007 Overvoltage
(active in operating states of
≤
o4)
The voltage at terminals 1U1, 1V1 or 1W1 and 3U1, 3W1 is higher than the response threshold (for longer than the “restart time”
set in P086).
Response threshold for armature supply voltage:
)
100%
P352
(1
P078.001
+
∗
Response threshold for field supply voltage:
)
100%
P352
(1
P078.002
+
∗
Possible fault causes
♦
Line
overvoltage
♦
Monitoring values set too sensitively or incorrectly (P352, P078)
NOTICE
This monitoring function is deactivated in the delivery state. It can be activated via parameter P820.
Fault value:
r047 Index 002 to 016:
1
Overvoltage has occurred
002 Number of phase that has activated fault message
0 ... Phase
UV
1 ... Phase
VW
2 ... Phase
WU
3 ... Phase
field
i003 Incorrect voltage value (normalized to 16384)
4
Undervoltage persists for longer than time set in
parameter P086 (if this is >0)
-
F008
Line frequency less than the minimum line frequency acc. to parameter P363
(active in operating states of
≤
o5)
This fault message is activated if the line frequency is less than the minimum line frequency
(for longer than the “restart time” set
in parameter P086).
Note: Up to software version 1.7 the threshold for activation of the fault message (minimum line frequency) is 45Hz.
Fault
value:
1
Frequency of the armature supply < minimum line frequency
2
Frequency of the field supply < minimum line frequency
4
Line frequency less than the minimum line frequency
for longer than set in parameter P086 (if >0)
F009
Line frequency greater than the maximum line frequency acc. to parameter P364
(active in operating states of
≤
o5)
This fault message is activated if the line frequency is greater than the maximum line frequency (for longer than the “restart time”
set in parameter P086).
Note: Up to software version 1.7 the threshold for activation of the fault message (maximum line frequency) is 65Hz
Fault
value:
1
Frequency of the armature supply > maximum line frequency
2
Frequency of the field supply > maximum line frequency
4
Line frequency greater than the maximum line frequency for longer than set in parameter P086 (if >0)
Summary of Contents for 6RA7013-6DV62
Page 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 733: ......