Chapter 4: Connecting External Equipment (Optional)
48
When connecting a DPX2 sensor package containing two DPX2
sensors:
A maximum of ten DX sensor packages can be cascaded because
12-2=10.
When connecting a DPX2 sensor package containing one DPX2
sensor:
A maximum of eleven DX sensor packages can be cascaded
because 12-1=11.
Using an Optional DPX3-ENVHUB4 Sensor Hub
A Raritan DPX3-ENVHUB4 sensor hub is physically and functionally
similar to the DPX-ENVHUB4 sensor hub, which increases the number
of sensor ports for the PX, except for the following differences:
All ports on the DPX3-ENVHUB4 sensor hub are RJ-45 instead of
RJ-12 as the DPX-ENVHUB4 sensor hub.
The DPX3-ENVHUB4 sensor hub supports all Raritan environmental
sensor packages, including DPX, DPX2, DPX3 and DX sensor
packages.
To connect diverse types of sensor packages to this sensor hub, you
must follow the combinations shown in the section titled
Mixing Diverse
Sensor Types
(on page 50).
To connect DPX3 sensor packages via the DPX3-ENVHUB4 hub:
1. Connect the DPX3-ENVHUB4 sensor hub to the PX using an RJ-12
to RJ-45 adapter cable.
a. Plug the RJ-45 connector of this cable into the IN port (Port 1) of
the hub.
b. Plug the RJ-12 connector of this cable into the RJ-12 SENSOR
port of the PX.
Summary of Contents for PX2-1000 SERIES
Page 5: ......
Page 71: ...Chapter 4 Connecting External Equipment Optional 52...
Page 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Page 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Page 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Page 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Page 627: ...Appendix K Integration 608 3 Click OK...
Page 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...