Chapter 4: Connecting External Equipment (Optional)
36
3. If intended, connect one DPX sensor package to the OUT port of the
differential air pressure sensor. It can be any DPX sensor package,
such as a DPX-T3H1.
The PX device
Raritan differential air pressure sensors
One DPX sensor package (optional)
Using an Optional DPX-ENVHUB4 Sensor Hub
Optionally, you can connect a Raritan
DPX-ENVHUB4
sensor hub to the
PX. This allows you to connect up to four DPX sensor packages to the
PX via the hub.
The DPX-ENVHUB4 sensor hub supports DPX sensor packages only.
Do NOT connect DPX2, DPX3 or DX sensor packages to this hub.
DPX-ENVHUB4 sensor hubs CANNOT be cascaded. You can only
connect one hub to each SENSOR port on the PX.
To connect DPX sensor packages via the DPX-ENVHUB4 hub:
1. Connect the DPX-ENVHUB4 sensor hub to the PX.
a. Plug one end of the Raritan-provided phone cable (4-wire, 6-pin,
RJ-12) into the IN port (Port 1) of the hub.
b. Plug the other end of the cable into the RJ-12 SENSOR port of
the PX.
2. Connect DPX sensor packages to any of the four OUT ports on the
hub.
Summary of Contents for PX2-1000 SERIES
Page 5: ......
Page 71: ...Chapter 4 Connecting External Equipment Optional 52...
Page 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Page 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Page 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Page 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Page 627: ...Appendix K Integration 608 3 Click OK...
Page 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...