497
In This Chapter
Maximum Ambient Operating Temperature ..........................................497
Serial RS-232 Port Pinouts....................................................................497
Sensor RJ-12 Port Pinouts....................................................................497
Feature RJ-45 Port Pinouts ...................................................................498
Maximum Ambient Operating Temperature
The maximum ambient operating temperature (TMA) for PX varies from
50 to 60 degrees Celsius, depending on the model and certification
standard (CE or UL). If necessary, contact Raritan Technical Support for
this information for your model.
Specification
Measure
Max Ambient Temperature
50 to 60 degrees Celsius
Serial RS-232 Port Pinouts
RS-232 Pin/signal definition
Pin No.
Signal
Direction
Description
1 DCD
Input
Data
2
RxD
Input
Receive data (data in)
3 TxD
Output
Transmit
data
4
DTR
Output
Data terminal ready
5 GND
―
Signal
ground
6
DSR
Input
Data set ready
7
RTS
Output
Request to send
8
CTS
Input
Clear to send
9 RI Input
Ring
indicator
Sensor RJ-12 Port Pinouts
Appendix A Specifications
Summary of Contents for PX2-1000 SERIES
Page 5: ......
Page 71: ...Chapter 4 Connecting External Equipment Optional 52...
Page 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Page 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Page 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Page 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Page 627: ...Appendix K Integration 608 3 Click OK...
Page 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...