Appendix C: Configuration or Firmware Upgrade with a USB Drive
506
fwupdate.cfg
The configuration file,
fwupdate.cfg
, is an ASCII text file containing
key-value pairs, one per line.
Each value in the file must be separated by a single = character, without
any surrounding spaces. Keys are not case sensitive.
This section only explains common options of the file.
Note: To use any options developed after version 2.2.13, the firmware
version running on your PX must be able to support them.
user
A required option.
Specify the name of a user account with Administrator Privileges.
For a PX with factory default configuration, set this option to
admin
.
password
A required option.
Specify the password of the specified admin user.
For a PX with factory default configuration, set this option to
raritan.
logfile
Specify the name of a text file where the PX will append the log
messages when interpreting the USB drive contents.
If the specified file does not exist in the USB drive, it will be
automatically created.
If this option is not set, no log message are recorded. The
disadvantage is that no feedback is available if the PX detects a
problem with the USB drive contents.
firmware
Specify the name of a firmware binary file used to upgrade your PX.
The specified firmware file must be compatible with your PX and
have an official Raritan signature.
If the specified firmware file is the same as the current firmware
version of your PX, no firmware upgrade is performed unless you
have set the option "force_update" to
true
.
force_update
Summary of Contents for PX2-1000 SERIES
Page 5: ......
Page 71: ...Chapter 4 Connecting External Equipment Optional 52...
Page 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Page 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Page 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Page 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Page 627: ...Appendix K Integration 608 3 Click OK...
Page 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...