Chapter 6: Using the Web Interface
282
Setting Thresholds for Multiple Sensors
You can configure thresholds for multiple environmental sensors of
the
same type
at a time. For example, if you want all temperature sensors to
have identical upper and lower thresholds, follow the procedure below to
set up all temperature sensors together.
To configure thresholds of multiple environmental sensors:
1. Click Peripheral Devices in the left pane.
2. Select the checkboxes of those environmental sensors whose
threshold settings should be the same. Make sure the selected
sensors belong to the same type.
To select all of those listed on the Peripheral Devices page,
simply select the checkbox in the header row.
3. Click Setup. Note that the Setup button is disabled if any of the
selected sensors belongs to a different type.
4. Configure the thresholds as described in
Configuring
Environmental Sensors or Actuators
(on page 278).
5. Click
OK.