Chapter 8: Using the Command Line Interface
458
config:#
sensor inlet <n> <sensor type> lowerCritical <option>
Set the Lower Warning threshold for an inlet sensor:
config:#
sensor inlet <n> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an inlet sensor:
config:#
sensor inlet <n> <sensor type> hysteresis <hy_value>
Set the assertion timeout for an inlet sensor:
config:#
sensor inlet <n> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the number of the inlet that you want to configure. For a
single-inlet PDU, <n> is always the number 1.
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
peakCurrent Peak
current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
lineFrequency
Line frequency sensor
residualCurrent
Residual current sensor
phaseAngle
Inlet phase angle sensor
Note: If the requested sensor type is not supported, the "Sensor is
not available" message is displayed.
Summary of Contents for PX2-1000 SERIES
Page 5: ......
Page 71: ...Chapter 4 Connecting External Equipment Optional 52...
Page 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Page 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Page 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Page 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Page 627: ...Appendix K Integration 608 3 Click OK...
Page 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...