![background image](http://html1.mh-extra.com/html/omron/cp1l-cpu-unit-03-2009/cp1l-cpu-unit-03-2009_operation-manual_742084327.webp)
293
Inverter Positioning
Section 5-3
ORIGIN SEARCH:
ORG(889)
ORG(889) performs an origin search or origin return operation.
• Origin Search:
Pulses are output to establish the origin based on origin proximity input
and origin input signals.
• Origin Return:
The positioning system is returned to the origin.
The parameters for pulse output 0 or pulse output 1 must be set in advance in
the PLC Setup to perform either an origin search or origin return operation.
MODE CONTROL: INI(880)
INI(880) changes the present value of inverter positioning or stops position-
ing.
F
First word of
starting fre-
quency
F (lower 4 dig-
its)
Starting Frequency in Hz
Pulse output 0 or 1: 0000 0000 to 0001 86A0
hex (0 to 100 kHz)
F+1 (upper 4
digits)
Operand
Description
Operand
Description
P
Port specifier
0020 hex: Inverter positioning 0
0021 hex: Inverter positioning 1
C
Control data
Bits 0 to 3
Not used: Always set to 0 hex
Bits 4 to 7
Not used: Always set to 0 hex
Bits 8 to 11
Not used: Always set to 0 hex
Bits 9 to 15
Mode
0 hex: Origin search
1 hex: Origin return
ORG(889)
P
C
C: Control data
P: Port specifier
Operand
Description
P
Port specifier
0020 hex: Inverter positioning 0
0021 hex: Inverter positioning 1
C
Control data
0002 hex: Changes the PV of the internal pulse
output.
0003 hex: Stops internal pulse output. Position-
ing will continue and the output value will not be
cleared.
0004 hex: Stops inverter positioning. Internal
pulse output will be stopped, positioning will be
stopped, and the output value will be cleared.
The next operation will not be accepted until the
error counter is cleared.
NP First word
with new PV
NP (lower 4
digits)
New PV
0000 0000 to FFFF FFFF hex
NP+1 (upper
4 digits)
INI(880)
C: Control data
P: Port specifier
NV: First word with new PV
P
C
NP
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...