477
CompoBus/S I/O Link Units
Section 7-6
Specifications
LED Indicators
CP1W-SRT21/CPM1A-SRT21 CompoBus/S I/O Link Unit
(1)
CompoBus/S Terminals
The following CompoBus/S terminals are provided: CompoBus/S com-
munications data high/low terminals, NC terminals for communications
power supply plus (
+
) and minus (
−
), and an NC terminal. (Power is sup-
plied internally for this Unit, so the NC terminals for communications
power supply can be used as relay terminals.)
Master PLC (CS Series)
CPU Unit
CP1L
I/O memory
Input
CIO 2
Output
CIO 12
8 bits
8 bits
I/O memory
Input
CIO 2004
Output
CIO 2000
8 bits
8 bits
CompoBus/S
Master Unit
Unit No. 0
CompoBus/S
I/O Link Unit
Node
number: 0
Model number
CP1W-SRT21/CPM1A-SRT21
Master/slave
CompoBus/S Slave
Number of I/O points
8 input points, 8 output points
Number of words allocated in
CPU Unit I/O memory
1 input word, 1 output word
(Allocated in the same way as Expansion Units and
Expansion I/O Units.)
Node number setting
Set using the DIP switch
(Set before turning on the CPU Unit’s power supply.)
Indicator
Name
Color
Meaning
COMM
Communications
Indicator
Yellow
ON:
Communications in progress.
OFF: Communications stopped or error
has occurred.
ERR
Error indicator
Red
ON:
A communications error has
occurred.
OFF: Indicates normal communications
or stand-by.
BD
NC(BS-)
NC
BD
NC(BS+)
S
COMM
ERR
ON
1
3
2
4 5
6
No.
SRT21
EXP
(1) CompoBus/S Terminals
(3) LED Indicators
(4) Expansion I/O Connecting Cable
(5) Expansion Connector
(2) DIP Switch
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...