613
Troubleshooting
Section 11-2
Errors Created with FALS Instructions
■
Reference Information
11-2-4 CPU Errors
■
CPU Unit Indicators
A CPU error or fatal error may have occurred if the ERR/ALM indicator lights
during operation (RUN mode or MONITOR mode), the RUN indicator turns
OFF, and operation stops.
CPU Errors
■
Reference Information
Note
Just as when a CPU error occurs, the RUN indicator will turn OFF and the
ERR/ALM indicator will light when a fatal error occurs. Connecting the CX-
Programmer, however, is possible for fatal errors but not for CPU errors. If the
CX-Programmer cannot be connected (online), a CPU error has probably
occurred.
Probable cause
Possible remedy
FALS instruction executed (FALS number 001)
C100 hex will be added to the FALS number (001 to 1FF hex)
and the result will be stored in A400 as the error code (C100 to
C2FF hex).
Check the conditions for executing FALS instructions and
remove any causes for the user-defined error.
Error flag
FALS Error Flag, A401.06
Error code (A400)
C101 to C2FF
Error information
---
POWER
Lit
RUN
Not lit
ERR/ALM
Lit
INH
---
BKUP
---
PRPHL
---
POWER
RUN
INH
PRPHL
BKUP
ERR/AL
Probable cause
Possible remedy
A WDT (watchdog) error occurred in the
CPU Unit. (This does not occur in normal
use.)
Cycle the power supply. The Unit may be
faulty. Consult your OMRON representa-
tive.
Error flag
None
Error code (A400)
None
Error information
None
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...