690
Auxiliary Area Allocations by Address
Appendix D
A400
All
Error code
When a non-fatal error (user-defined
FALS(006) or system error) or a fatal
error (user-defined FALS(007) or
system error) occurs, the 4-digit
hexadecimal error code is written to
this word. When two or more errors
occur simultaneously, the highest
error code will be recorded.
---
Cleared
Cleared
Refreshed
when error
occurs.
---
A401
A401.00 Other Fatal
Error Flag
ON when a fatal error that is not
defined for A401.01 to A401.15
occurs. Detailed information is output
to the bits of A314.
There are no errors that affect this
flag at this time. This flag is reserved
by the system.
OFF: No
other fatal
error
ON: Other
fatal error
Cleared
Cleared
Refreshed
when error
occurs.
A314
A401.06 FALS Error
Flag
(fatal error)
ON when a fatal error is generated
by the FALS(006) instruction. The
CPU Unit will stop operating and the
ERR/ALM indicator will light.
The corresponding error code will be
written to A400. Error codes C101 to
C2FF correspond to FALS numbers
001 to 511.
This flag will be turned OFF when
the FALS errors are cleared.
ON:
FALS(006)
executed
OFF:
FALS(006)
not executed
Cleared
Cleared
Refreshed
when error
occurs.
A400
A401.08 Cycle Time
Too Long Flag
(fatal error)
ON if the cycle time exceeds the
maximum cycle time set in the PLC
Setup (the cycle time monitoring
time). CPU Unit operation will stop
and the ERR/ALM indicator on the
front of the CPU Unit will light.
This flag will be turned OFF when
the error is cleared.
OFF: Cycle
time under
max.
ON: Cycle
time over
max.
Cleared
Cleared
Refreshed
when the
cycle time
exceeds
maximum.
PLC
Setup
(Cycle
time moni-
toring
time)
A401.09 Program Error
Flag
(fatal error)
ON when program contents are
incorrect.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light. The task num-
ber where the error occurred will be
stored in A294 and the program
address will be stored in A298 and
A299.
The type of program error that
occurred will be stored in A295.08 to
A295.15. Refer to the description of
A295 for more details on program
errors.
This flag will be turned OFF when
the error is cleared.
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A294,
A295,
A298 and
A299
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...