![background image](http://html1.mh-extra.com/html/omron/cp1l-cpu-unit-03-2009/cp1l-cpu-unit-03-2009_operation-manual_742084430.webp)
396
Memory Cassette Functions
Section 6-6
b.
Select the
Data Memory
Option in the
Backup to Flash Memory
Area
and click the
Backup
Button.
The DM data will be written to the built-in flash memory.
Note
The DM data that is saved and written at startup is the entire DM Area (D0 to
D32767).
PLC Setup
1,2,3...
1.
Set
Do not detect Low Battery (run without battery)
to
Do not detect
.
2.
Set
IOM Hold Bit Status at Startup
and
Forced Status Hold Bit Status at
Startup
to
Clear (OFF)
.
3.
Set
Read DM from flash memory
to
Read
. (Only when DM initial values
have been saved as described above.)
!Caution
The CP1L CPU Units automatically back up the user program and parameter
data to flash memory when these are written to the CPU Unit. Also, the CX-
Programmer can be used to save all of the data in the DM Area to the flash
memory for use as initial values when the power supply is turned ON. Neither
of these functions saves the I/O memory data (including HR Area data,
counter PVs and Completion Flags, and DM Area data other than initial val-
ues). The HR Area data, counter PVs and Completion Flags, and DM Area
data other than initial values are held during power interruptions with a bat-
tery. If there is a battery error, the contents of these areas may not be accu-
rate after a power interruption. If HR Area data, counter PVs and Completion
Flags, and DM Area data other than initial values are used to control external
outputs, prevent inappropriate outputs from being made whenever the Battery
Error Flag (A402.04) is ON.
6-6
Memory Cassette Functions
6-6-1
Overview
CP1L CPU Units have Memory Cassette functions that enable data in the
CPU Unit to be stored on and read from a special CP1W-ME05M Memory
Cassette. These functions can be used for the following applications.
• Copying data to other CPU Units to produce duplicate devices.
• Backing up data in case the CPU Unit needs to be replaced due to any
malfunction.
• Writing and updating data when existing device versions are upgraded.
Memory Cassette
Specifications
Use the following Memory Cassette.
Model
Specifications
CP1W-ME05M
• Memory size
512 Kwords
• Storage capacity The following CPU Unit data (for each Unit)
• User programs
• Parameters
• Comment memory
• Function Block (FB) sources
• DM initial values in the built-in flash memory
• DM in RAM
• Write method
Operations from the CX-Programmer
• Read method
Powering up with DIP switch pin SW2 set to
ON, or operations from the CX-Programmer
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...