416
Failure Diagnosis Functions
Section 6-8
3.
Set the error code and error to be simulated as the second operand (two
words) of FAL(006) or FALS(007). Indicate a nonfatal error for FAL(006)
and a fatal error for FALS(007).
To simulate more than one system error, use more than one FAL(006) or
FALS(007) instruction with the same value in A529 and different values for the
second operand.
Auxiliary Area Flags and Words
Example for a Battery Error
Note
Use the same methods as for actual system errors to clear the simulated sys-
tem errors. Refer to the
11-2 Troubleshooting
for details. All system errors
simulated with FAL(006) and FALS(007) can be cleared by cycling the power
supply.
6-8-4
Output OFF Bit
As an emergency measure when an error occurs, all outputs from Output
Units can be turned OFF by turning ON the Output OFF Bit (A500.15). The
operating mode will remain in RUN or MONITOR mode, but all outputs will be
turned OFF.
Note
Normally (when IOM Hold Bit = OFF), all outputs from Output Units are turned
OFF when the operating mode is changed from RUN/MONITOR mode to
PROGRAM mode. The Output OFF Bit can be used to turn OFF all outputs
without switching to PROGRAM mode.
Application Precaution for
DeviceNet
When the CPM1A-DRT21 is used, all slave outputs will be turned OFF, i.e., all
inputs to the master will be OFF.
Name
Address
Operation
FAL/FALS Number
for System Error
Simulation
A529
Set a dummy FAL/FALS number to use to simu-
late a system error.
0001 to 01FF hex: FAL/FALS numbers 1 to 511
0000 or 0200 to FFFF hex: No FAL/FALS number
for system error simulation.
MOV
&100
A529
a
MOV
#00F7
D10
FAL
100
D10
Execution condition
Set FAL number 100 in A529.
Set error code for battery error
(#00F7) in D10.
Generate a battery error using FAL
number 100.
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...