524
LCD Option Board Function
Section 8-6
4.
Use the
Up
button to change the value to
0100
.
5.
Press the
OK
button to save the setting.
The column cursor will return to the digit before the value.
6.
Use the
Down
button to move the cursor to line 2.
Note
Only when the cursor is on the digit before the value, press the
Down
or
Up
button to b move the cursor to other lines.
7.
Use the
Forward
button to move the column cursor to the sign position.
Press the
Down
or
Up
button to change the sign to
-
.
8.
Press the
OK
button to save the setting.
If the setting is invalid, the screen display will have no change.
9.
Press the
ESC
button to return to the User Monitor Screen.
The average has been changed to 0100, but the minimum is still +00123.
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...