Inverter Positioning
Section 5-3
5-3-7
Determining the Internal Pulse Output Frequency
Use the following formula to calculate the internal pulse frequency (Hz) to out-
put from the pulse output instruction (e.g., PLS2) based on the power supply
frequency (Hz) to be output from the inverter to the motor.
Note
(1) Calculate the power supply frequency for one revolution per second from
the motor specifications. For example, with a 1,800-r/min (60-Hz) motor
(30 r/s), the power supply frequency for one revolution per second would
be calculated as follows: 60 [Hz]
÷
30 [r/s] = 2 [Hz].
D
First destina-
tion word for
present value
D
Lower 4
digits
When a present value is read, the following
data is stored in D and D+1 as an 8-digit hexa-
decimal value.
P = #0020/#0021: The actual movement from
the internal pulse origin.
P = #0030/#0031: The present value of the
error counter.
D+1 Upper 4
digits
Destination
word for
inverter posi-
tioning status
(P = #0020 or
#0021)
D
Bit 0
Operation Command Flag
ON: Operation command in progress
OFF: Stopped
Bit 1
Forward Command Flag
ON: Forward command in progress
OFF: Reverse command in progress or
stopped
Bit 2
Reverse Command Flag
ON: Reverse command in progress
OFF: Forward command in progress or
stopped
Bit 3
In-position Flag
ON: In position
OFF: Not in position
Bit 4
Error Counter Error Flag
ON: Error occurred in error counter
OFF: No error
Bit 5
Internal Pulse Output Flag
ON: Pulses being output
OFF: Pulse output stopped
Bit 6
Internal Pulse Acceleration/Deceleration Flag
ON: Acceleration/deceleration in progress for
internal pulse output (i.e., frequency being
changed)
OFF: Constant frequency for internal pulse out-
put
Bit 7
Error Counter Alarm Flag
ON: Alarm occurred for error counter
OFF: No alarm
Bit 15
Error Counter Sign Flag
ON: Positive
OFF: Negative
Operand
Description
Frequency of
internal pulse
output (Hz)
Power supply
frequency to
motor (Hz)
Encoder resolution
(pulses/revolution)
Power supply frequency to motor
for one revolution per second (See note 1.)
High-speed
counter multiplier
Gear ratio between motor
shaft and encoder shaft
(See note 2.)
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...