233
Pulse Outputs
Section 5-2
An origin search will not be started unless the origin search proximity speed is
less than the origin search high speed and unless the origin search/return ini-
tial speed is less than the origin search proximity speed.
Origin Search Error Processing
The CP1L CPU Unit's pulse output function performs a basic error check
before starting to output pulses (when the instruction is executed) and will not
output pulses if the settings are incorrect. There are other errors that can
occur with the origin search function during pulse output, which may stop the
pulse output.
If an error occurs that stops pulse output, the pulse output's Output Stopped
Error Flag will be turned ON and the Pulse Output Stop Error Code will be
written to Error Code word. Use these flags and error codes to identify the
cause of the error.
The Pulse Output Stop Errors will not affect the CPU Unit's operating status.
(The Pulse Output Stop Errors do not cause a fatal or non-fatal error in the
CPU Unit.)
Related Auxiliary Area Flags
Pulse Output Stop Error Codes
Positioning with absolute
pulse specification
Cannot be used.
Positioning with relative
pulse specification
Outputs the specified number of pulses after setting the
current position to 0.
Function
Operation
Function
Pulse output number
0
1
Output Stopped Error Flags
ON when an error occurred while outputting pulses in the ori-
gin search function.
0: No error
1: Stop error occurred.
A280.07
A281.07
Stop Error Codes
When a Pulse Output Stop Error occurs, the error code is stored in that pulse outputs corre-
sponding Stop Error Code word.
A444
A445
Error name
Error code
Likely cause
Corrective action
Operation after
error
CW Limit Stop Input
Signal
0100
Stopped due to a CW limit signal
input.
Move in the CCW direction.
Immediate stop,
No effect on
other port
CCW Limit Stop
Input Signal
0101
Stopped due to a CCW limit sig-
nal input.
Move in the CW direction.
No Origin Proximity
Input Signal
0200
The parameters indicate that the
Origin Proximity Input Signal is
being used, but a Origin Proxim-
ity Input Signal was not received
during the origin search.
Check the wiring of the Origin
Proximity Input Signal as well as
the PLC Setup's Origin Proxim-
ity Input Signal Type setting (NC
or NO) and execute the origin
search again. Turn the power
supply OFF and then ON if the
signal type setting was changed.
No effect on
other port
No Origin Input Sig-
nal
0201
The Origin Input Signal was not
received during the origin
search.
Check the wiring of the Origin
Input Signal as well as the PLC
Setup's Origin Input Signal Type
setting (NC or NO) and execute
the origin search again. Turn the
power supply OFF and then ON
if the signal type setting was
changed.
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...