429
Analog Input Units
Section 7-2
■
Set Data
• The Analog Input Unit will not start converting analog I/O values until the
range code has been written.
• Once the range code has been set, it is not possible to change the setting
while power is being supplied to the CPU Unit. To change the I/O range,
turn the CPU Unit OFF then ON again.
Averaging
Set whether averaging is to be used for set data. When the averaging bit is set
to 1, the average (moving average) for the past eight inputs is output as con-
version data.
Reading Analog Input
Conversion Values
Read the conversion value storage area with the ladder program. With word m
as the last input word allocated to the CPU Unit or an already-connected
Expansion Unit, the A/D conversion data will be output to the following words
m+1 to m+4.
Startup Operation
After the power is turned ON, it will require two cycle times plus approximately
50 ms before the first conversion data is stored in the input words. Therefore,
create a program as shown below, so that when operation begins simulta-
neously with startup it will wait for valid conversion data.
The analog input data will be 0000 until the initial processing is completed.
Handling Unit Errors
• When an error occurs in an Analog Input Unit, the analog input conversion
data becomes 0000.
15 0
1 0 0 0 0 0 0
8 7 6 5 4 3 2 1
15 0
1 0 0 0 0 0 0
8 7 6 5 4 3 2 1
0
0
Set to 1.
Set to 1.
Wd (n+1)
Wd (n+2)
Analog input 1
Analog input 2
Analog input 3
Analog input 4
Averaging
0
No
1
Yes
Input Use
0
No
1
Yes
Range code
Analog input signal range
−
10 to 10 V
0 to 10 V
1 to 5 V or 4 to 20 mA
0 to 5 V or 0 to 20 mA
00
01
10
11
MOV(021)
2
D 0
T 5
#0002
T5
Power ON
P_On
TIM5 is started when the power is
turned ON. After 0.1 to 0.2 s (100 to
200 ms) elapses, the TIM5 contact
turns ON and the analog input 1 con-
version data stored in word 2 is trans-
ferred to DM0.
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...