656
Auxiliary Area Allocations by Function
Appendix C
Power Supply Information
Flash Memory Backup Information
Name
Address
Description
Access
Updated
Startup Time
A510 and
A511
These words contain the time at which the power was
turned ON. The contents are updated every time that the
power is turned ON. The data is stored in BCD.
A510.00 to A510.07: Second (00 to 59)
A510.08 to A510.15: Minute (00 to 59)
A511.00 to A511.07: Hour (00 to 23)
A511.08 to A511.15: Day of month (01 to 31)
Read/write
Power Interruption Time
A512 and
A513
These words contain the time at which the power was
interrupted. The contents are updated every time that the
power is interrupted. The data is stored in BCD.
A512.00 to A512.07: Second (00 to 59)
A512.08 to A512.15: Minute (00 to 59)
A513.00 to A513.07: Hour (00 to 23)
A513.08 to A513.15: Day of month (01 to 31)
(These words are not cleared at startup.)
Read/write
Number of Power
Interruptions
A514
Contains the number of times that power has been inter-
rupted since the power was first turned ON. The data is
stored in binary. To reset this value, overwrite the current
value with 0000.
Read/write
Total Power ON Time
A523
Contains the total time that the PLC has been ON in 10-
hour units. The data is stored in binary and it is updated
every 10 hours. To reset this value, overwrite the current
value with 0000.
Read/write
Name
Address
Description
Access
Updated
User Program Date
A90 to A93 These words contain in BCD the date and time that the
user program was last overwritten.
A90.00 to A90.07: Seconds (00 to 59)
A90.08 to A90.15: Minutes (00 to 59)
A91.00 to A91.07: Hour (00 to 23)
A91.08 to A91.15: Day of month (01 to 31)
A92.00 to A92.07: Month (01 to 12)
A92.08 to A92.15: Year (00 to 99)
A93.00 to A93.07: Day of the week (00 to 06)
(00: Sunday, 01: Monday, 02: Tuesday, 03: Wednesday,
04: Thursday, 05: Friday, 06: Saturday)
Read-only
Parameter Date
A94 to A97 These words contain in BCD the date and time that the
parameters were last overwritten.
A94.00 to A94.07: Seconds (00 to 59)
A94.08 to A94.15: Minutes (00 to 59)
A95.00 to A95.07: Hour (00 to 23)
A95.08 to A95.15: Day of month (01 to 31)
A96.00 to A96.07: Month (01 to 12)
A96.08 to A96.15: Year (00 to 99)
A97.00 to A97.07: Day of the week (00 to 06)
(00: Sunday, 01: Monday, 02: Tuesday, 03: Wednesday,
04: Thursday, 05: Friday, 06: Saturday)
Read-only
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...